• Contents of D8420
2. Cautions on use
Do not use both the parameters and communication format setting devices (D8120 or D8420) at the same
time. If the communication format is set using both methods at the same time, priority is given to the setting
using parameters.
When setting the communication format device (D8120) in an FX
0N
PLC, set the communication setting
latched (battery backed) device (M8120) to ON.
When using computer link, make sure to set the header (b8) and terminator (b9) to "not provided". And set the
protocol (b14) to "used".
If the communication format is set using the special data register, the setting becomes valid when the power
is turned ON after the setting is written to the special data register.
9.2.9
Station number settings [D8121 and D8421]
These devices set the station number in computer link.
1. Detailed contents
Set the station number of each PLC used in computer link. The applicable setting range is from 0 to 15 (from
H00 to H0F).
In FX
1S
, FX
1N
, FX
1NC
, FX
2N
, FX
2NC
, FX
3S
, FX
3G
, FX
3GC
, FX
3U
and FX
3UC
PLCs, the contents set using
parameters are stored when the power is turned ON.
In FX
2
(FX), FX
2C
and FX
0N
PLCs, set the station number using a sequence program, and then turn ON the
power.
In all PLCs except FX
3G
, FX
3GC
, FX
3U
and FX
3UC
PLCs and in FX
3G
, FX
3GC
, FX
3U
and FX
3UC
PLCs using
communication port ch1, use D8121.
Set the station number using parameters when using the communication port ch2 in FX
3G
, FX
3GC
, FX
3U
and
FX
3UC
PLCs.
Use D8421 for confirmation.
2. Cautions on use
Do not use both the parameters and station number settings device (D8121) at the same time. If the station
number is set using both methods at the same time, priority is given to the setting using a parameter.
When setting the station number settings device (D8121) in an FX
0N
PLC, set the communication setting
latched (battery backed) device (M8120) to ON.
Bit No.
Name
Contents
0 (bit = OFF)
1 (bit = ON)
b0
Data length
7-bit
8-bit
b1
b2
Parity
b2, b1
(0, 0): Not provided
(0, 1): Odd
(1, 1): Even
b3
Stop bit
1-bit
2-bit
b4
b5
b6
b7
Baud rate
(bps)
b7, b6, b5, b4
b7, b6, b5, b4
(0, 0, 1, 1): 300
(0, 1, 1, 1): 4800
(0, 1, 0, 0): 600
(1, 0, 0, 0): 9600
(0, 1, 0, 1): 1200
(1, 0, 0, 1): 19200
(0, 1, 1, 0): 2400
(1, 0, 1, 0): 38400
b8
Header
Not provided
Provided
b9
Terminator
Not provided
Provided
b10
b11
b12
Control line
Com-
puter
link
b12, b11, b10
(0, 0, 0): RS-485/RS-422 interface
(0, 1, 0): RS-232C interface
b13
Sum check
Not added
Added
b14
Protocol
Not used
Used
b15
Control
procedure
Format 1
Format 4
Summary of Contents for FX-485ADP
Page 2: ......
Page 120: ...B 2 FX Series PLC User s Manual Data Communication Edition N N Network ...
Page 188: ...C 2 FX Series PLC User s Manual Data Communication Edition Parallel Link ...
Page 244: ...D 2 FX Series PLC User s Manual Data Communication Edition Computer Link ...
Page 344: ...E 2 FX Series PLC User s Manual Data Communication Edition Inverter Communication ...
Page 700: ...H 2 FX Series PLC User s Manual Data Communication Edition Programming Communication ...
Page 752: ...I 2 FX Series PLC User s Manual Data Communication Edition Remote Maintenance ...
Page 817: ......