E-54
FX Series PLC User's Manual - Data Communication Edition
Inverter Communication
5 Communication Setting in Inverter
5.3 E500 Series (When Connected to PU Port)
5.3.2
Parameter setting method (reference)
This subsection explains the parameter setting method using the operation panel.
For details on the operation panel, refer to the respective inverter manual.
The operating procedure example below shows a case in which the baud rate is set to 19200 bps.
1
Confirming the RUN indicator and the operation mode indicator
Confirm that the operation is stopped (that the RUN indicator is Off).
2
Selecting the parameter setting mode
Press the MODE key, and select the parameter setting mode.
*1.
The frequency setting mode is displayed only in the PU operation mode.
3
Reading the parameter (Pr. 118)
There are two methods to read the parameter number:
• Method to read the parameter number using the UP and DOWN keys
Press the UP and DOWN keys, and display the parameter number to be read.
When the cover is closed
Unit indicator
Operation status indication
The LEDs light and flash according
to the mode and operation status.
UP/DOWN key
Change the set value of the
frequency and parameters.
Display LED 4 digits
Displays the frequency,
parameter number, etc.
MODE key
Changes over the mode.
Setting key
Sets each setting.
When the cover is open
Monitoring mode
Frequency setting mode
*1
Parameter setting mode
Summary of Contents for FX-485ADP
Page 2: ......
Page 120: ...B 2 FX Series PLC User s Manual Data Communication Edition N N Network ...
Page 188: ...C 2 FX Series PLC User s Manual Data Communication Edition Parallel Link ...
Page 244: ...D 2 FX Series PLC User s Manual Data Communication Edition Computer Link ...
Page 344: ...E 2 FX Series PLC User s Manual Data Communication Edition Inverter Communication ...
Page 700: ...H 2 FX Series PLC User s Manual Data Communication Edition Programming Communication ...
Page 752: ...I 2 FX Series PLC User s Manual Data Communication Edition Remote Maintenance ...
Page 817: ......