FX Series PLC User's Manual - Data Communication Edition
Inverter Communication
5 Communication Setting in Inverter
5.5 V500, F500 and A500 Series (Connection to FR-A5NR)
A
Comm
on I
te
ms
B
N:
N N
etwo
rk
C
Paral
le
l Li
nk
D
Com
puter Li
nk
E
In
verter
C
omm
uni
cation
F
N
on-Proto
col
C
ommunicati
on
(R
S/RS
2 Instru
ction
)
G
No
n-
Protoc
ol
Co
mmuni
ca
tion
(FX
2N
-2
32IF)
H
Programm
ing
Comm
uni
cation
I
Re
mo
te
Ma
intenance
Apx.A
D
isco
nti
nued
models
5.5
V500, F500 and A500 Series (Connection to FR-A5NR)
5.5.1
Contents of parameter setting
1. Contents of communication setting (essential items)
The table below shows parameters which should be set in all cases.
2. Parameters which should be adjusted between test operation and actual operation
3. Others (which should be set if necessary)
The table below shows parameters to be considered when using various system configuration and inverters.
For the method of use, refer to the respective inverter manual.
5.5.2
Parameter setting method (reference)
The parameter setting method is the same as that for the V500, F500 and A500 Series (connection to the PU port).
For the parameter setting method, refer to Subsection 5.4.2.
Parameter No.
Parameter item
Set value
Setting contents
Pr331
Communication station number
00 to 31
Up to eight inverters can be connected.
Pr332
Communication speed
48
4800 bps
96
9600 bps (standard)
192
19200 bps
Pr333
Stop bit / Data length
10
Data length: 7-bit/Stop bit: 1-bit
Pr334
Parity check presence/absence
2
2: Even parity
Pr337
Waiting time setting
9999
Set in communication data
Pr341
CR, LF presence/absence selection
1
CR: Provided, LF: Not provided
Pr79
Operation mode selection
0
External operation mode is selected when
power is turned ON.
Pr340
Link startup mode selection
1
Computer link
Pr336
Communication check time interval
9999
Communication check is stopped.
Parameter No.
Parameter item
Set value
Setting contents
Pr335
Number of communication
retries
9999
Set the value shown on the left during adjustment,
and set a value from 1 to 10 during operation.
Parameter No.
Parameter item
Set value
Setting contents
Pr342
EEPROM write selection
0 or 1
0: EEPROM is written.
1: RAM is written.
Pr338
Operation command right
0 or 1
0: PLC
1: Outside
Pr339
Speed command write
0 or 1
0: PLC
1: Outside
Summary of Contents for FX-485ADP
Page 2: ......
Page 120: ...B 2 FX Series PLC User s Manual Data Communication Edition N N Network ...
Page 188: ...C 2 FX Series PLC User s Manual Data Communication Edition Parallel Link ...
Page 244: ...D 2 FX Series PLC User s Manual Data Communication Edition Computer Link ...
Page 344: ...E 2 FX Series PLC User s Manual Data Communication Edition Inverter Communication ...
Page 700: ...H 2 FX Series PLC User s Manual Data Communication Edition Programming Communication ...
Page 752: ...I 2 FX Series PLC User s Manual Data Communication Edition Remote Maintenance ...
Page 817: ......