5 Communication Setting in Inverter
5.6 E700, D700 Series (when PU port, FR-E7TR is connected)
5.6
E700, D700 Series (when PU port, FR-E7TR is connected)
5.6.1
Contents of parameter setting
1. Contents of communication setting (essential items)
The table below shows parameters which should be set in all cases.
2. Parameters which should be adjusted between test operation and actual operation
Caution on setting the PU communication check time interval (Pr122)
Parameter No.
Parameter item
Set value
Setting contents
Pr117
PU communication station number
00 to 31 Up to eight inverters can be connected.
Pr118
PU communication speed
48
4800 bps
96
9600 bps
192
19200 bps (standard)
384
38400 bps
Pr119
PU communication stop bit length
10
Data length: 7-bit/Stop bit: 1-bit
Pr120
PU communication parity check
2
2: Even parity
Pr123
PU communication waiting time setting
9999
Set in communication data
Pr124
PU communication CR/LF presence/
absence selection
1
CR: Provided, LF: Not provided
Pr79
Operation mode selection
0
External operation mode is selected when
power is turned ON.
Pr549
Protocol selection
0
Mitsubishi inverter (computer link
operation) protocol
Pr340
Communication startup mode selection
1 or 10
1: Network operation mode
10: Network operation mode
Operation mode can be changed
between the PU operation mode and
network operation mode from the
operation panel.
Parameter No.
Parameter item
Set value
Setting contents
Pr121
Number of PU communication retries
9999
Set the value shown on the left during
adjustment, and set a value from 1 to 10
during operation.
Pr122
PU communication check time interval
9999
Set the value shown on the left during
adjustment, and set a proper value in
accordance with the system specification
during operation.
Description
Set value
During adjustment or when communication with the PLC is not executed periodically
9999
When communication with the PLC is not executed
0 (Initial Value)
Set the communication time in the following cases
• When it is necessary to monitor absence of communication for a certain time and stop
the inverter in such a case while communication with the PLC is being executed
• When it is necessary to stop the motor at the point which the PLC mode is changed
from RUN to STOP
0.1 to 999.8 sec
Summary of Contents for FX-485ADP
Page 2: ......
Page 120: ...B 2 FX Series PLC User s Manual Data Communication Edition N N Network ...
Page 188: ...C 2 FX Series PLC User s Manual Data Communication Edition Parallel Link ...
Page 244: ...D 2 FX Series PLC User s Manual Data Communication Edition Computer Link ...
Page 344: ...E 2 FX Series PLC User s Manual Data Communication Edition Inverter Communication ...
Page 700: ...H 2 FX Series PLC User s Manual Data Communication Edition Programming Communication ...
Page 752: ...I 2 FX Series PLC User s Manual Data Communication Edition Remote Maintenance ...
Page 817: ......