E-68
FX Series PLC User's Manual - Data Communication Edition
Inverter Communication
5 Communication Setting in Inverter
5.8 F800 and A800 Series (when built-in RS-485 terminal is connected)
5.8.2
Parameter setting method (reference)
This subsection explains the parameter setting method using the operation panel.
For details on the operation panel, refer to the respective inverter manual.
The operating procedure example below shows a case in which the baud rate is set to 19200 bps.
1
Confirming the RUN indicator and the operation mode indicator
Confirm that the operation is stopped (that the P.RUN indicator is off).
2
Selecting the parameter setting mode
Press the MODE key, and select the parameter setting mode.
3
Setting the parameter Pr. 160 to "0"
(This step is not required if Pr. 160 is already set to "0".)
1. Turn the setting dial until "Pr. 160" is displayed.
2. Press the SET key to read the current set value.
3. Turn the setting dial, and change the set value to "0".
Hz
FR-DU08
PU
EXT
NET
MON
PRM
IM
PM
P.RUN
STOP
STOP
REV
REV
FWD
FWD
ESC
SET
MODE
PU
EXT
RESET
RESET
Rotation direction key
FWD: Lit during forward rotation
REV : Lit during reverse rotation
MODE key
Changes over the mode.
SET key
Sets each setting.
Setting dial
Used to change the frequency
setting and parameter values.
Monitor (5-digit LED)
shows the frequency,
parameter number, etc.
Operation mode indicator
NET : Lit to indicate network
operation mode
MODE
Monitor/frequency
setting mode
Parameter setting mode
The previously read parameter
is displayed.
SET
Summary of Contents for FX-485ADP
Page 2: ......
Page 120: ...B 2 FX Series PLC User s Manual Data Communication Edition N N Network ...
Page 188: ...C 2 FX Series PLC User s Manual Data Communication Edition Parallel Link ...
Page 244: ...D 2 FX Series PLC User s Manual Data Communication Edition Computer Link ...
Page 344: ...E 2 FX Series PLC User s Manual Data Communication Edition Inverter Communication ...
Page 700: ...H 2 FX Series PLC User s Manual Data Communication Edition Programming Communication ...
Page 752: ...I 2 FX Series PLC User s Manual Data Communication Edition Remote Maintenance ...
Page 817: ......