E-120
FX Series PLC User's Manual - Data Communication Edition
Inverter Communication
10 Practical Program Examples (FX3S, FX3G, FX3GC, FX3U, FX3UC)
10.1 Practical Example 1
10.1.3 Program example
1. Writing parameters to an inverter while the PLC is in RUN mode
*1.
When using an E500 Series inverter, use "H2" to specify computer link operation.
*2.
The FX
3S
, FX
3G
and FX
3GC
PLC does not support the IVBWR instruction. Use the IVWR instruction
instead.
M8002
FNC271
IVDR
K0
H0FD
H9696
K1
FNC271
IVDR
K0
H0FB
H0
*1
K1
Initial pulse
SET
M10
FNC 12
MOV
K1
D200
P
FNC 12
MOV
K12000
D201
P
FNC 12
MOV
K2
D202
P
FNC 12
MOV
K500
D203
P
FNC 12
MOV
K7
D204
P
FNC 12
MOV
K10
D205
P
FNC 12
MOV
K8
D206
P
FNC 12
MOV
K10
D207
P
FNC274
IVBWR
*2
K0
K4
D200
K1
The write
instruction is
driven
Driving of
write
instruction
M10
M8029
RST
M10
The inverter is reset
Computer link
operation is
specified
The maximum
frequency (Pr. 1) is
specified
The maximum
frequency (Pr. 1) is
set to "120 Hz"
The minimum
frequency (Pr. 2) is
specified
The minimum
frequency (Pr. 2) is
set to "5 Hz"
The acceleration time
(Pr. 7) is specified
The acceleration time
(Pr. 7) is set to "1 sec"
The deceleration time
(Pr. 8) is specified
The deceleration time
(Pr. 8) is set to "1 sec"
The parameters are written
all at once
D200 to D207
(Pr. 1, Pr. 2, Pr. 7 and Pr. 8)
Driving of
write
instruction
Instruction execute
complete
Summary of Contents for FX-485ADP
Page 2: ......
Page 120: ...B 2 FX Series PLC User s Manual Data Communication Edition N N Network ...
Page 188: ...C 2 FX Series PLC User s Manual Data Communication Edition Parallel Link ...
Page 244: ...D 2 FX Series PLC User s Manual Data Communication Edition Computer Link ...
Page 344: ...E 2 FX Series PLC User s Manual Data Communication Edition Inverter Communication ...
Page 700: ...H 2 FX Series PLC User s Manual Data Communication Edition Programming Communication ...
Page 752: ...I 2 FX Series PLC User s Manual Data Communication Edition Remote Maintenance ...
Page 817: ......