E-135
FX Series PLC User's Manual - Data Communication Edition
Inverter Communication
11 Troubleshooting
11.4 Checking Sequence Program
A
Comm
on I
te
ms
B
N:
N N
etwo
rk
C
Paral
le
l Li
nk
D
Com
puter Li
nk
E
In
verter
C
omm
uni
cation
F
N
on-Proto
col
C
ommunicati
on
(R
S/RS
2 Instru
ction
)
G
No
n-
Protoc
ol
Co
mmuni
ca
tion
(FX
2N
-2
32IF)
H
Programm
ing
Comm
uni
cation
I
Re
mo
te
Ma
intenance
Apx.A
D
isco
nti
nued
models
4. Presence of VRRD and VRSC instructions
1) Except FX
3G
, FX
3U
and FX
3UC
PLCs
Verify that the VRRD and VRSC instructions are not used in the program.
If these instructions are used, delete them, turn OFF the PLC power, and then turn the power ON again.
2) In FX
3G
PLC
- In the case of the 14 points and 24-point type
Verify that the VRRD and VRSC instructions are not used in the program.
If these instructions are used, delete them, turn OFF the PLC power, and then turn the power ON again.
- In the case of the 40 points and 60-point type
Verify that the VRRD and VRSC instructions are not used in the program.
If these instructions are used in the program, the communication function is not available in ch2.
Use ch1, or delete these instructions.
After deleting these instructions, turn OFF the PLC power, and then turn the power ON again.
3) In FX
3U
and FX
3UC
PLCs
Verify that the VRRD and VRSC instructions are not used in the program.
If these instructions are used in the program, the communication function is not available in ch1.
Use ch2, or delete these instructions.
After deleting these instructions, reboot the PLC's power.
5. Presence of RS instruction (in FX
2N
and FX
2NC
PLCs)
Verify that the RS instruction is not used in the program.
If this instruction is used, delete it, turn OFF the PLC power, and then turn the power ON again.
6. Presence of RS and RS2 instructions (in FX
3S
, FX
3G
, FX
3GC
, FX
3U
and FX
3UC
PLCs)
Verify that the RS and RS2 instructions are not being used for the same channel.
If these instructions are used for the same channel, delete them, turn OFF the PLC power, and then turn the
power ON again.
7. Presence of ADPRW instructions (in FX
3S
, FX
3G
, FX
3GC
, FX
3U
and FX
3UC
PLCs)
Verify that the ADPRW instructions are not being used for the same channel.
If these instructions are used for the same channel, delete them, and reboot the PLC’s power.
8. Presence of FLCRT, FLDEL, FLWR, FLRD, FLCMD, and FLSTRD instructions (in FX
3U
and
FX
3UC
PLCs)
Verify that the FLCRT, FLDEL, FLWR, FLRD, FLCMD and FLSTRD instructions are not being used for the
same channel.
If these instructions are used for the same channel, delete them, reboot the PLC’s power.
11.4.1 Checking inverter operation status
1. When the operation mode of an inverter is not changed over to computer link mode
1) Verify that the inverter is set to the external operation mode.
2) Verify that no signal is being input to the external terminals STF and STR.
3) Verify that the correct operation mode changeover program is being executed.
2. When an inverter cannot be started even in computer link mode
1) Verify that the program for starting the inverter is executed correctly.
2) Verify that the operation command and speed command are set correctly.
3) Verify that the allowable communication time interval is set correctly.
3. When an inverter is stopped by an alarm during operation due to defective communication
1) Verify that a communication cable is connected correctly between the PLC and the inverter.
(Check for poor contact or wire breakage.)
2) Verify that a sequence program is created so that communication is executed with each inverter within a
constant cycle. Set the communication check time interval to a large value, and check the communication
status.
3) Verify that the allowable communication time interval is set correctly.
4) Verify that terminal resistors are wired correctly.
Summary of Contents for FX-485ADP
Page 2: ......
Page 120: ...B 2 FX Series PLC User s Manual Data Communication Edition N N Network ...
Page 188: ...C 2 FX Series PLC User s Manual Data Communication Edition Parallel Link ...
Page 244: ...D 2 FX Series PLC User s Manual Data Communication Edition Computer Link ...
Page 344: ...E 2 FX Series PLC User s Manual Data Communication Edition Inverter Communication ...
Page 700: ...H 2 FX Series PLC User s Manual Data Communication Edition Programming Communication ...
Page 752: ...I 2 FX Series PLC User s Manual Data Communication Edition Remote Maintenance ...
Page 817: ......