12.4.9 Communication format setting [D8370, D8400 and D8420]
These devices set the communication format.
1. Detailed contents
These devices can set the data length, parity, baud rate, etc.
When communication port ch0 is used, D8370 sets the communication format.
When communication port ch1 is used, D8400 sets the communication format.
When communication port ch2 is used, D8420 sets the communication format.
The table below shows the contents of the communication format settings. Computer link setting is not
applicable for D8370, D8400.
*1.
Make sure to set as "0" when using computer link.
*2.
In RS2 instruction, up to four headers and up to four terminators can be set.
*3.
The control line is not available in FX
3G
, FX
3GC
PLCs when ch0 is used. Set "(1, 1, 1)".
*4.
When executing non-protocol communication using RS2 instruction, add the sum check after the
terminators.
Make sure to set the terminators when adding the sum check.
*5.
Make sure to set as "0" when using non-protocol communication.
2. Cautions on use
• In FX
3S
, FX
3U
and FX
3UC
PLCs, the communication format can be set using parameters.
• Even if the communication format is changed while the RS2 instruction is being driven, it is not reflected.
• In FX
3G
and FX
3GC
PLCs, the communication format can be set only for ch1 and ch2 using parameters.
Bit No.
Name
Contents
0 (bit = OFF)
1 (bit = ON)
b0
Data length
7-bit
8-bit
b1
b2
Parity
b2, b1
(0, 0): Not provided
(0, 1): Odd
(1, 1): Even
b3
Stop bit
1-bit
2-bit
b4
b5
b6
b7
Baud rate
(bps)
b7, b6, b5, b4
b7, b6, b5, b4
(0, 0, 1, 1): 300
(0, 1, 1, 1): 4800
(0, 1, 0, 0): 600
(1, 0, 0, 0): 9600
(0, 1, 0, 1): 1200
(1, 0, 0, 1): 19200
(0, 1, 1, 0): 2400
(1, 0, 1, 0): 38400
b8
*1
Header
Not provided
Provided
*2
b9
*1
Terminator
Not provided
Provided
*2
b10
b11
b12
Control line
Non-protocol
communication
*3
b12, b11, b10
(0, 0, 0): Not provided <RS-232C interface>
(0, 0, 1): Standard mode <RS-232C interface>
(0, 1, 0): Interlink mode <RS-232C interface>
(0, 1, 1): Modem mode <RS-232C interface>
(1, 1, 1): Communication in accordance with RS-485
<RS-485/RS-422 interface>
Computer link
b12, b11, b10
(0, 0, 0): RS-485/RS-422 interface
(0, 1, 0): RS-232C interface
b13
Sum check
Not added
Added
*4
b14
*5
Protocol
Not used
Used
b15
Control
procedure
(CR, LF)
Non-protocol
communication
CR, LF: Not used
(Format 1)
Non-protocol
communication
CR, LF: Used
(Format 2)
Computer link
CR, LF: Not used
(Format 1)
Computer link
CR, LF: Used
(Format 4)
Summary of Contents for FX-485ADP
Page 2: ......
Page 120: ...B 2 FX Series PLC User s Manual Data Communication Edition N N Network ...
Page 188: ...C 2 FX Series PLC User s Manual Data Communication Edition Parallel Link ...
Page 244: ...D 2 FX Series PLC User s Manual Data Communication Edition Computer Link ...
Page 344: ...E 2 FX Series PLC User s Manual Data Communication Edition Inverter Communication ...
Page 700: ...H 2 FX Series PLC User s Manual Data Communication Edition Programming Communication ...
Page 752: ...I 2 FX Series PLC User s Manual Data Communication Edition Remote Maintenance ...
Page 817: ......