7 Troubleshooting
7.7 Checking Programming Tool Setting
7.7
Checking Programming Tool Setting
Verify that the setting contents in the programming tool are correct.
1. Checking the communication port
Verify that the communication port is set correctly.
2. Checking the transmission speed
Verify that the transmission speed is set correctly.
For the programming tool setting, refer to Chapter 6.
7.8
Checking Absence/Presence of Errors
1. Checking M8062 (except FX
3S
, FX
3G
, FX
3GC
, FX
3U
and FX
3UC
PLCs)
When a communication error occurs in the standard built-in port, M8062 turns ON and D8062 stores the
corresponding error code.
2. Checking the error code (D8062)
D8062 stores either of the following error codes:
3. Checking M8063 and M8438
When a communication errors occur in optional communication equipment, M8063 turns ON and D8063
stores the corresponding error code during communication using ch1, and M8438 turns ON and D8438 stores
the corresponding error code during communication using ch2.
Error code
Contents of error
D8062
6201
*1
Parity error, overrun error or framing error
6202
Defective communication character
6203
Communication data sum mismatch
6204
Defective data format
6205
Defective command
Summary of Contents for FX-485ADP
Page 2: ......
Page 120: ...B 2 FX Series PLC User s Manual Data Communication Edition N N Network ...
Page 188: ...C 2 FX Series PLC User s Manual Data Communication Edition Parallel Link ...
Page 244: ...D 2 FX Series PLC User s Manual Data Communication Edition Computer Link ...
Page 344: ...E 2 FX Series PLC User s Manual Data Communication Edition Inverter Communication ...
Page 700: ...H 2 FX Series PLC User s Manual Data Communication Edition Programming Communication ...
Page 752: ...I 2 FX Series PLC User s Manual Data Communication Edition Remote Maintenance ...
Page 817: ......