21 - 10
21.3 GOT Side Settings
The following shows the applicable combinations of connection types, the number of channels, and restricted
functions.
: Allowed : Restricted
*1
When the functions below are used, the connectable number of channels may be restricted depending on the combination of the
functions to be used.
• Barcode function • RFID function • Remote personal computer operation function
• Video display function (GT27 only) •Multimedia function (GT27 only) • External I/O function
• RGB display function (GT27 only) • Report function • Sound output function
The video display function, multimedia function and RGB display function cannot be used together.
For details, refer to the following.
➠
21.3.4 Determining the GOT side interface (Interface selection)
*2
For the FA transparent function via the RS-232 connection, the RS-232 interface built in the GOT is available only.
When the RS-232 interface built in the GOT is already used, the FA transparent function is not available.
*3
When a GOT and PLC are connected by Ethernet connection, connecting a GOT and a personal computer by Ethernet is not
allowed.
Serial
connection
Third party PLC connection (serial connection)
Non-Mitsubishi Electric Products 2
• 12. CONNECTION TO LS INDUSTRIAL SYSTEMS PLC
• 15. CONNECTION TO SIEMENS PLC
Third party safety controller connection
Non-Mitsubishi Electric Products 2
• 14. CONNECTION TO SICK SAFETY CONTROLLER
Third party servo amplifier connection
Non-Mitsubishi Electric Products 1
• 14. CONNECTION TO PANASONIC SERVO AMPLIFIER
Third party robot controller connection
Non-Mitsubishi Electric Products 1
• 2. CONNECTION TO IAI ROBOT CONTROLLER
Third party temperature controller connection
Non-Mitsubishi Electric Products 1
• 3. CONNECTION TO AZBIL CONTROL EQUIPMENT
• 5. CONNECTION TO OMRON TEMPERATURE CONTROLLER
• 10. CONNECTION TO SHINKO TECHNOS INDICATING CONTROLLER
• 11. CONNECTION TO CHINO CONTROLLER
Non-Mitsubishi Electric Products 2
• 5. CONNECTION TO FUJI SYS TEMPERATURE CONTROLLER
• 8. CONNECTION TO YOKOGAWA TEMPERATURE CONTROLLER
• 9. CONNECTION TO RKC TEMPERATURE CONTROLLER
Microcomputer Connection (Serial)
Microcomputers, MODBUS/Fieldbus Products, Peripherals
• 2. MICROCOMPUTER CONNECTION (SERIAL)
MODBUS/RTU connection
Microcomputers, MODBUS/Fieldbus Products, Peripherals
• 5. MODBUS/RTU CONNECTION
Item
Allowable combination of connection types
GOT to be used
Functions that are restricted by the connection type
*1
GT27
FA transparent function
RS-232
USB
Ethernet
(a)
• Bus/network connection: 1 channel
• Serial connection: 1 to 3 channels
Max. 4 channels
*2
(b)
• Bus/network connection: 1 channel
• Ethernet connection: 1 to 3 channels
Max. 4 channels
*2
*3
(c)
• Ethernet connection: 1 to 3 channels
• Serial connection: 1 to 3 channels
Max. 4 channels
*2
*3
(d)
• Bus/network connection: 1 channel
• Ethernet connection: 1 to 2 channels
• Serial connection: 1 to 2 channels
Max. 4 channels
*2
*3
(e)
• Serial connection: 4 channels
Max. 4 channels
*2
(f)
• Ethernet connection: 4 channels
Max. 4 channels
*2
Connection type
Reference
Summary of Contents for GOT2000 Series
Page 2: ......
Page 84: ......
Page 432: ...6 58 6 6 Precautions ...
Page 578: ...9 54 9 6 Precautions ...
Page 726: ...12 84 12 5 Precautions ...
Page 756: ......
Page 822: ...14 66 14 4 Device Range that Can Be Set ...
Page 918: ...15 96 15 7 Precautions ...
Page 930: ...16 12 16 6 Precautions ...
Page 964: ......
Page 1002: ...19 38 19 7 Precautions ...
Page 1022: ...20 20 20 5 Precautions ...
Page 1023: ...MULTI CHANNEL FUNCTION 21 MULTI CHANNEL FUNCTION 21 1 ...
Page 1024: ......
Page 1054: ...21 30 21 5 Multi channel Function Check Sheet ...
Page 1055: ...FA TRANSPARENT FUNCTION 22 FA TRANSPARENT FUNCTION 22 1 ...
Page 1056: ......
Page 1223: ......