3.1 Access Range for Monitoring Stations on Network Systems
3 - 3
3
ACCESS
R
ANGE FOR MONIT
O
RIN
G
(2) When connecting to QCPU (Q mode)/QnACPU/AnUCPU
• The GOT can monitor the control station and all the normal stations on the network.
• The GOT can monitor the control station and all the normal stations on other networks.
(For monitoring stations on other networks, be sure to set the routing parameter)
When the Universal model QCPU is used as a relay station, the GOT can monitor stations with the station No.65 or
later in the CC-Link IE controller network.
• When connected to a relay station and the data link system is included, the master station and local stations can be
monitored.
• When connected to a relay station, it is not necessary to designate the data link parameter [Effective unit number
for accessing other stations] for the PLC CPU of the connected station. (Even if designated, the parameter is
ignored)
• Devices of other stations (other than devices B and W that are allocated by the network parameter) may not allow
monitoring depending on their PLC CPU.
➠ ■7.
Monitor accessible range of other stations and setting method of monitor devices (Examples
1 to 2)
*1
The control station and normal station correspond to the master station and local station in the CC-Link IE field network
respectively.
GOT
Normal
station
Normal
station
Normal
station
Control
station
*1
*1
GOT
Normal
station
Normal
station
Normal
station
Normal
station
Control
station
Normal
station
Control
station
GOT
Normal
station
Normal
station
M station
L station
Control
station
Normal
station
Control
station
L station
Summary of Contents for GOT2000 Series
Page 2: ......
Page 84: ......
Page 432: ...6 58 6 6 Precautions ...
Page 578: ...9 54 9 6 Precautions ...
Page 726: ...12 84 12 5 Precautions ...
Page 756: ......
Page 822: ...14 66 14 4 Device Range that Can Be Set ...
Page 918: ...15 96 15 7 Precautions ...
Page 930: ...16 12 16 6 Precautions ...
Page 964: ......
Page 1002: ...19 38 19 7 Precautions ...
Page 1022: ...20 20 20 5 Precautions ...
Page 1023: ...MULTI CHANNEL FUNCTION 21 MULTI CHANNEL FUNCTION 21 1 ...
Page 1024: ......
Page 1054: ...21 30 21 5 Multi channel Function Check Sheet ...
Page 1055: ...FA TRANSPARENT FUNCTION 22 FA TRANSPARENT FUNCTION 22 1 ...
Page 1056: ......
Page 1223: ......