4.2 MELSEC Q Series
4 - 75
4
HOW T
O
MONIT
O
R REDUNT
ANT SYSTEM
4.2.9
Switch the Monitor Target to the Control System Using the Script
Function
The following explains how to create a script screen, to be used for the MELSECNET/H or MELSECNET/10 connection
(network system), or Ethernet connection, that automatically changes the monitoring target (Station No.) at the occurrence
of system switching even if the MELSEC redundant setting is not made.
The script executes the station number switching function or screen switching function.
The following shows the advantages and disadvantages of the station number switching function and screen switching
function.
The following explains how to use each function.
■1.
Method for using the station number switching function
• As a feature of this function, monitor screens for Station No. 1 (control system) and Station No. 2 (standby system)
can be created on one screen.
• If the system switching occurs, the GOT can change the monitoring target to the control system PLC CPU on the
same monitor screen.
• To achieve this, the script of the GOT monitors the special relay SM1515 (Control system identification flag) of the
PLC CPU and stores the station number of the latest control system into the station number switching device.
• Restrictions: Some objects do not allow the station number to be switched.
➠
GT Designer3 (GOT2000) Screen Design Manual
(1) Setting method (For MELSECNET/H connection, MELSECNET/10 connection)
System configuration example 1: MELSECNET/H connection, MELSECNET/10 connection
Function
Advantage
Disadvantage
Station number switching
function
The monitor screens for Station No. 1 (control system) and
Station No. 2 (standby system) can be created on one screen.
Some objects do not allow the station number to be switched.
Screen switching function
All objects can be used since monitor screens are created for
each station number.
Monitor screens must be created separately for Station No. 1
(control system) and Station No. 2 (standby system).
Connected module
Network No.
Station No.
MELSECNET/H network module of control system
1
1
MELSECNET/H network module of standby system
2
GOT connected to MELSECNET/H network or MELSECNET/10 network
3
MELSECNET/H
(MELSECNET/H mode or MELSECNET/10 mode)
Network No. 1
GOT
Station
No. 3
Control system
(System A)
Q25PRH
CPU
QJ71
BR11
Standby system
(System B)
Station No. 1
Q25PRH
CPU
QJ71
BR11
Station No. 2
Summary of Contents for GOT2000 Series
Page 2: ......
Page 84: ......
Page 432: ...6 58 6 6 Precautions ...
Page 578: ...9 54 9 6 Precautions ...
Page 726: ...12 84 12 5 Precautions ...
Page 756: ......
Page 822: ...14 66 14 4 Device Range that Can Be Set ...
Page 918: ...15 96 15 7 Precautions ...
Page 930: ...16 12 16 6 Precautions ...
Page 964: ......
Page 1002: ...19 38 19 7 Precautions ...
Page 1022: ...20 20 20 5 Precautions ...
Page 1023: ...MULTI CHANNEL FUNCTION 21 MULTI CHANNEL FUNCTION 21 1 ...
Page 1024: ......
Page 1054: ...21 30 21 5 Multi channel Function Check Sheet ...
Page 1055: ...FA TRANSPARENT FUNCTION 22 FA TRANSPARENT FUNCTION 22 1 ...
Page 1056: ......
Page 1223: ......