4.2 MELSEC Q Series
4 - 83
4
HOW T
O
MONIT
O
R REDUNT
ANT SYSTEM
Step 2.
Set the trigger action.
Set the trigger action so that the station number is switched when the faulty station information (SW70) of
MELSECNET/H turns ON in the project specified by choosing [Common]
[trigger action].
Make the setting so that the station number is switched when the faulty station information (GS231) from
the station monitoring specified by selecting [Common]
[trigger action] turns ON.
Condition 1 : SW70.b0 (while ON)
When b0 is ON, Station No. 1 is abnormal.
Operation
: GD100=2
Screen No. is changed to 2.
Condition 1 : SW70.b1 (while ON)
When b1 is ON, Station No. 2 is abnormal.
Operation
: GD100=1
Screen No. is changed to 1.
Condition 1 : GS231.b0 (while ON)
When b0 is ON, Station No. 1 is abnormal.
Operation
: GD100=2
Screen No. is changed to 2.
Condition 1 : GS231.b1 (while ON)
When b1 is ON, Station No. 2 is abnormal.
Operation
: GD100=1
Screen No. is changed to 1.
Summary of Contents for GOT2000 Series
Page 2: ......
Page 84: ......
Page 432: ...6 58 6 6 Precautions ...
Page 578: ...9 54 9 6 Precautions ...
Page 726: ...12 84 12 5 Precautions ...
Page 756: ......
Page 822: ...14 66 14 4 Device Range that Can Be Set ...
Page 918: ...15 96 15 7 Precautions ...
Page 930: ...16 12 16 6 Precautions ...
Page 964: ......
Page 1002: ...19 38 19 7 Precautions ...
Page 1022: ...20 20 20 5 Precautions ...
Page 1023: ...MULTI CHANNEL FUNCTION 21 MULTI CHANNEL FUNCTION 21 1 ...
Page 1024: ......
Page 1054: ...21 30 21 5 Multi channel Function Check Sheet ...
Page 1055: ...FA TRANSPARENT FUNCTION 22 FA TRANSPARENT FUNCTION 22 1 ...
Page 1056: ......
Page 1223: ......