5.4 PLC Side Setting
5 - 75
5
E
T
H
E
RNET CONNEC
T
ION
■3.
[Network parameter] of GX Developer
(1) Network parameter
: Necessary : As necessary : Not necessary
*1
Specify the same network No. as that of the GOT.
*2
Do not set the same station No. as that of the GOT.
POINT
POINT
POINT
When changing the network parameter
After writing the network parameter to the PLC CPU, operate the PLC CPU ether turning OFF
and then ON or resetting.
Item
Set value
Setting necessity at GOT connection
Network type
Ethernet (fixed)
Start I/O No.
0000H
Network No.
*1
1
Group No.
0 (fixed)
Station No.
*2
2
IP address
192.168.0.19
Station No.<->IP information
(Use default value)
FTP Parameters
Router relay parameter
Routing parameters
Refer to (2)