5 - 106
5.5 Precautions
(2) System configuration example 2
In the multiple CPU configuration, the GOT cannot access the CPU module on the other network via the CPU No.
(“MELSOFT Connection Extended Setting”: “Use”) and relaying the network module that is controlled by the other
CPU No. (“MELSOFT Connection Extended Setting”: “Not use” or “MELSOFT Connection Extended Setting” is not
supported).
(a)
System configuration figure
1) Counter measures
Take one of the following counter measures.
• Change “MELSOFT Connection Extended Setting” at the PLC side.
Set “MELSOFT Connection Extended Setting” to “Use” in the CPU module No. 2 whose “MELSOFT
Connection Extended Setting” is available.
➠
QnUCPU User's Manual (Communication via Built-in Ethernet Port)
• Change “Ethernet setting” at the GOT side.
Set the port No. of the connected equipment to [5006] by “Ethernet setting” at the GOT side.
➠
GOT
CPU
module
No. 1
CPU
module
No. 2
“MELSOFT Connection Extended Setting”: “Use”
Ethernet
“MELSOFT Connection Extended Setting”: “Not use”
“Ethernet setting”
Port No. of the connected equipment:
[5001]
Ethernet
module
CPU
module
Ethernet
Ethernet module that
the CPU No. 2 controls
Summary of Contents for GOT2000 Series
Page 2: ......
Page 84: ......
Page 432: ...6 58 6 6 Precautions ...
Page 578: ...9 54 9 6 Precautions ...
Page 726: ...12 84 12 5 Precautions ...
Page 756: ......
Page 822: ...14 66 14 4 Device Range that Can Be Set ...
Page 918: ...15 96 15 7 Precautions ...
Page 930: ...16 12 16 6 Precautions ...
Page 964: ......
Page 1002: ...19 38 19 7 Precautions ...
Page 1022: ...20 20 20 5 Precautions ...
Page 1023: ...MULTI CHANNEL FUNCTION 21 MULTI CHANNEL FUNCTION 21 1 ...
Page 1024: ......
Page 1054: ...21 30 21 5 Multi channel Function Check Sheet ...
Page 1055: ...FA TRANSPARENT FUNCTION 22 FA TRANSPARENT FUNCTION 22 1 ...
Page 1056: ......
Page 1223: ......