5.5 Precautions
5 - 107
5
E
T
H
E
RNET CONNEC
T
ION
(3) System configuration example 3
(a)
System configuration figure-1
In the system configuration where the Ethernet module is mounted on the same CPU base, when the network
Nos. of the CPU built-in Ethernet port and Ethernet module are duplicated, the GOT cannot access the other
CPU No. in the multiple configuration via the CPU built-in Ethernet port (“MELSOFT Connection Extended
Setting” to “Use”).
1) Counter measures
Take one of the following counter measures.
• Change “Ethernet setting” at the GOT side.
Set the port No. of the connected equipment to [5006] by “Ethernet setting” at the GOT side.
➠
• Change the connection route
Connect the GOT to the CPU module No. 2 via the Ethernet module.
GOT
CPU
module
No. 1
CPU
module
No. 2
N/W No.:
1
Station No.: 1
IP address: 192.168.3.39
“MELSOFT Connection Extended Setting”: “Use”
Ethernet
“Ethernet setting”
Port No. of the connected equipment:
[5001]
Ethernet
module
N/W No.:
1
Station No.: 10
IP address: 192.168.3.10
The network No. is duplicated.
GOT
Ethernet
CPU
module
No. 1
CPU
module
No. 2
Ethernet
module
Summary of Contents for GOT2000 Series
Page 2: ......
Page 84: ......
Page 432: ...6 58 6 6 Precautions ...
Page 578: ...9 54 9 6 Precautions ...
Page 726: ...12 84 12 5 Precautions ...
Page 756: ......
Page 822: ...14 66 14 4 Device Range that Can Be Set ...
Page 918: ...15 96 15 7 Precautions ...
Page 930: ...16 12 16 6 Precautions ...
Page 964: ......
Page 1002: ...19 38 19 7 Precautions ...
Page 1022: ...20 20 20 5 Precautions ...
Page 1023: ...MULTI CHANNEL FUNCTION 21 MULTI CHANNEL FUNCTION 21 1 ...
Page 1024: ......
Page 1054: ...21 30 21 5 Multi channel Function Check Sheet ...
Page 1055: ...FA TRANSPARENT FUNCTION 22 FA TRANSPARENT FUNCTION 22 1 ...
Page 1056: ......
Page 1223: ......