6 - 48
6.4 GOT Side Settings
POINT
POINT
POINT
The settings of connecting equipment can be confirmed in [I/F Communication Setting].
For details, refer to the following:
➠
1.1.3 I/F communication setting
6.4.2
Communication detail settings
Make the settings according to the usage environment.
■1.
Serial (MELSEC)(GT27, GT25, GT23)
*1
This is effective when collecting a large data on other than the monitor screen (logging, recipe function, etc.). However, when
connecting to Q00J/Q00/Q01CPU, the sequence scan time may be influenced. If you want to avoid the influence on the
sequence scan time, do not set [High(Normal)].
(High performance is hardly affected)
*2
Set this item if you want to avoid the influence on the sequence scan time further than the [Middle] setting when connecting to
Q00UJ/Q00U/Q01U/Q02UCPU or Q00J/Q00/Q01CPU. However, the monitor speed may be reduced.
*3
The format setting differs depending on the controller.
L6ADP-R4 adapter : [2]
Other than L6ADP-R4 adapter: [1]
*4
When using a global label, to read or write more than 235 two-byte characters, set the [Monitor speed] to [High (Standard)] or
[Middle].
If [Monitor speed] is set to [Low], a system error occurs when reading or writing.
For details, refer to the following manual.
➠
GT Designer3 (GOT2000) Screen Design Manual
Item
Description
Range
Transmission Speed
Set this item when change the transmission speed used for communication
with the connected equipment.
(Default: 115200bps)
When the setting exceeds the limit of the connected equipment,
communication is performed at the fastest transmission speed supported by
the connected equipment.
9600bps, 19200bps, 38400bps,
57600bps, 115200bps
Retry
Set the number of retries to be performed when a communication timeout
occurs.
(Default: 0time)
0 to 5times
Timeout Time
Set the time period for a communication to time out.
(Default: 3sec)
1 to 30sec
Delay Time
Set this item to adjust the transmission timing of the communication request
from the GOT.
(Default: 0ms)
0 to 300 (ms)
Format
*3
Select the communication format.
(Default: 1)
1, 2
Monitor Speed
*4
Set the monitor speed of the GOT.
This setting is not valid in all systems.
(Default: Normal)
High(Normal)
*1
Middle
Low
*2
Servo axis switching GD
device head No.
Set the servo axis switching GD device head No.
(Default: 10)
For details, refer to the following POINT.
➠
(3) Indirect specification of the servo axis No.
0 to 65520
Summary of Contents for GOT2000 Series
Page 2: ......
Page 84: ......
Page 432: ...6 58 6 6 Precautions ...
Page 578: ...9 54 9 6 Precautions ...
Page 726: ...12 84 12 5 Precautions ...
Page 756: ......
Page 822: ...14 66 14 4 Device Range that Can Be Set ...
Page 918: ...15 96 15 7 Precautions ...
Page 930: ...16 12 16 6 Precautions ...
Page 964: ......
Page 1002: ...19 38 19 7 Precautions ...
Page 1022: ...20 20 20 5 Precautions ...
Page 1023: ...MULTI CHANNEL FUNCTION 21 MULTI CHANNEL FUNCTION 21 1 ...
Page 1024: ......
Page 1054: ...21 30 21 5 Multi channel Function Check Sheet ...
Page 1055: ...FA TRANSPARENT FUNCTION 22 FA TRANSPARENT FUNCTION 22 1 ...
Page 1056: ......
Page 1223: ......