9.6 Precautions
9 - 53
MELSECNET/H C
O
NNE
CTION (PLC T
O
PLC N
ETWORK),
MELSECNET/10 CONNECTION (PLC T
O
PLC NETWORK)
9
(Improvement measure)
(a)
Add unit on PLC side
Add a unit on the PLC side to disperse the GOT access destinations.
(b)
Split the network
Split the network to disperse the GOT access.
GOT
GOT
GOT
GOT
GOT
GOT
Add station No. 2 to disperse the GOT access
Access to station No. 2
Access to station No. 1
station
No. 2
station
No. 1
GOT
GOT
GOT
GOT
GOT
GOT
Split the network to disperse the GOT access