14.2 System Configuration
14 - 41
INVERTER
C
O
NNE
CTION
14
(d)
Pr.999=13
*1
Before configuring the automatic batch setting, if Pr.414 is set to 1, the setting is not changed.
(4) Communication settings of inverter (Manual setting)
Set the following parameters using the PU (operation panel or parameter unit). Before setting the parameters, set
Pr.160 (User group read selection) to 0 so that simple mode + extended parameters are displayed. (The default value
of FREQROL-F800 is 9999.)
Do not change these parameters, even though they can be monitored from the GOT. If they are changed,
communication with the GOT is disabled.
*1
Setting items are parameter names described in the manual of FREQROL-A800, F800 series.
*2
Settings on the GOT can be changed.
When changing the settings on the GOT, be sure to change the parameters on the inverter to correspond with the GOT settings.
*3
Since the value has been set as a default, no setting is required when connecting to the PU connector on the inverter side.
*4
To use the FREQROL 800 driver, set 0.
*5
Inverter default values (No need to change).
*6
The inverter side setting defaults to 0 (invalid).
To use the PLC function, set 1 or 2.
Pr.No.
Setting item
Set value
79
Operation mode selection
0
332
RS-485 communication speed
1152
333
RS-485 communication stop bit length
0
334
RS-485 communication parity check
1
335
RS-485 communication retry count
9999
336
RS-485 communication check time interval
9999
337
RS-485 communication waiting time setting
0ms
340
Communication startup mode selection
1
341
RS-485 communication CR/LF selection
1
414
PLC function operation selection
2
*1
549
Protocol selection
0
Setting item
*1
Parameter No.
Set value
Contents of setting
PU connector
RS-485
PU communication station number/
RS-485 communication station number
Pr.117
Pr.331
0 to 31
➠
PU communication speed/
RS-485 communication speed
*2
Pr.118
Pr.332
192
*3
19200bps
PU communication stop bit length/data length/
RS-485 communication stop bit length/data length
*2
Pr.119
Pr.333
10
*4
Data length: 7bit
Stop bit length: 1bit
PU communication parity check/
RS-485 communication parity check
*2
Pr.120
Pr.334
1
Odd
Number of PU communication retries/
RS-485 communication retry count
Pr.121
Pr.335
9999
The inverter will not come to an
alarm stop.
PU communication check time interval/
RS-485 communication check time interval
Pr.122
Pr.336
9999
*3
Communication check suspension
PU communication waiting time setting/
RS-485 communication waiting time setting
Pr.123
Pr.337
0
0ms
PU communication CR/LF selection/
RS-485 communication CR/LF selection
Pr.124
Pr.341
1
*5
With CR, without LF
Protocol selection
-
Pr.549
0
*5
Mitsubishi Electric inverter protocol
Operation mode selection
Pr.79
PU connector
1
PU operation mode
RS-485
0
*5
External operation mode at power
on
Communication startup mode selection
Pr.340
PU connector
0
*5
Refer to Pr.79 settings.
RS-485
1
Network operation mode.
Communication EEPROM write selection
Pr.342
0
*5
Written to RAM and EEPROM
PLC function operation selection
*6
Pr.414
1, 2
Enabled with 1 and 2.
Summary of Contents for GOT2000 Series
Page 2: ......
Page 84: ......
Page 432: ...6 58 6 6 Precautions ...
Page 578: ...9 54 9 6 Precautions ...
Page 726: ...12 84 12 5 Precautions ...
Page 756: ......
Page 822: ...14 66 14 4 Device Range that Can Be Set ...
Page 918: ...15 96 15 7 Precautions ...
Page 930: ...16 12 16 6 Precautions ...
Page 964: ......
Page 1002: ...19 38 19 7 Precautions ...
Page 1022: ...20 20 20 5 Precautions ...
Page 1023: ...MULTI CHANNEL FUNCTION 21 MULTI CHANNEL FUNCTION 21 1 ...
Page 1024: ......
Page 1054: ...21 30 21 5 Multi channel Function Check Sheet ...
Page 1055: ...FA TRANSPARENT FUNCTION 22 FA TRANSPARENT FUNCTION 22 1 ...
Page 1056: ......
Page 1223: ......