5.2 System Configuration
5 - 17
5
E
T
H
E
RNET CONNEC
T
ION
5.2.4
Connection to CC-Link IE Field Network Ethernet Adapter Module
*1
The destination connected with the twisted pair cable varies with the configuration of the applicable Ethernet network system.
Connect to the Ethernet module, hub, transceiver, or other system equipment corresponding to the applicable Ethernet network
system.
Use cables, connectors, and hubs that meet the IEEE802.3 10BASE-T/100BASE-TX standard.
A cross cable is available for connecting the GOT to the Ethernet module.
*2
A length between a hub and a node.
The maximum distance differs depending on the Ethernet device to be used.
The following shows the number of the connectable nodes when a repeater hub is used.
• 10BASE-T: Max. 4 nodes for a cascade connection (500m)
• 100BASE-TX: Max. 2 nodes for a cascade connection (205m)
When switching hubs are used, the cascade connection between the switching hubs has no logical limit for the number of
cascades.
For the limit, contact the switching hub manufacturer.
*3
Use cables with the following specifications.
*4
For the system configuration on the CC-Link IE Field Network module side, refer to the following manual.
➠
CC-Link IE Field Network Ethernet Adapter Module User's Manual
*5
The number of connectable GOTs for one network is 63 units (at most).
*6
GT25-W, GT2505-V does not support the option device.
PLC
Connection cable
1)
*4
CC-Link IE
Field Network
Ethernet adapter module
Connection cable 2)
*1
GOT
Number of
connectable
equipment
Model
name
CC-Link
IE Field
Network
Master/
Local
module
Cable
model
Max.
distance
Communication
type
Model
name
Communication
type
Cable model
Connection
diagram
number
Maximu
m
segment
length
*3
Option
device
*6
Model
MELSEC-
Q
(Q mode)
Motion
Controller
CPU
(Q Series)
QJ71G
F11-
T2
*4
Double-
shielded
twisted
pair
cable
*3
100m
CC-Link IE
NZ2G
F-ETB
Ethernet
• 100BASE-TX
Shielded
twisted pair
cable (STP)
or unshielded
twisted pair
cable (UTP)
of category 5
or higher
• 10BASE-T
Shielded
twisted pair
cable (STP)
or unshielded
twisted pair
cable (UTP)
of category 3
or higher
100m
- (Built
into
GOT)
128 GOTs
*5
(recommen
ded to 16
units or
less)
GT25-
J71E71
-100
Connector
Range
Category 5e or higher
Shielded RJ-45
Cable that satisfies the following specifications:
IEEE802.3 1000BASE-T
ANSI/TIA/EIA-568-B(Category 5e)
Communication driver
Ethernet(MITSUBISHI ELECTRIC),Gateway
CC-Link IE Field
Network Master/
Local module
CC-Link IE
Field Network
Ethernet adapter
module
GOT
QCPU
Connection cable 1)
Connection cable 2)
Summary of Contents for GOT2000 Series
Page 2: ......
Page 84: ......
Page 432: ...6 58 6 6 Precautions ...
Page 578: ...9 54 9 6 Precautions ...
Page 726: ...12 84 12 5 Precautions ...
Page 756: ......
Page 822: ...14 66 14 4 Device Range that Can Be Set ...
Page 918: ...15 96 15 7 Precautions ...
Page 930: ...16 12 16 6 Precautions ...
Page 964: ......
Page 1002: ...19 38 19 7 Precautions ...
Page 1022: ...20 20 20 5 Precautions ...
Page 1023: ...MULTI CHANNEL FUNCTION 21 MULTI CHANNEL FUNCTION 21 1 ...
Page 1024: ......
Page 1054: ...21 30 21 5 Multi channel Function Check Sheet ...
Page 1055: ...FA TRANSPARENT FUNCTION 22 FA TRANSPARENT FUNCTION 22 1 ...
Page 1056: ......
Page 1223: ......