8.3 GOT Side Settings
8 - 33
8
BU
S CON
NECTION
8.3.2
Communication detail settings
■1.
Bus(Q)
*1
This range is effective when collecting a large amount of data (such as logging and recipe function) on other than the monitor
screen.
However, the range may affect the sequence scan time when connecting to Q00UJ/Q00U/Q01U/Q02UCPU or Q00J/Q00/
Q01CPU.
If you want to avoid the influence on the sequence scan time, do not set [High(Normal)].
(This setting hardly affects QCPUs other than the above.)
*2
Set this range if you want to avoid the influence on the sequence scan time further than the [Middle] setting when connecting to
Q00UJ/Q00U/Q01U/Q02UCPU or Q00J/Q00/Q01CPU.
However, the monitor speed may be reduced.
*3
When using a global label, to read or write more than 235 two-byte characters, set the [Monitor speed] to [High (Standard)] or
[Middle].
If [Monitor speed] is set to [Low], a system error occurs when reading or writing.
For details, refer to the following manual.
➠
GT Designer3 (GOT2000) Screen Design Manual
■2.
Bus(A/QnA)
POINT
POINT
POINT
(1) Communication interface setting by Utility
The communication interface setting can be changed on the Utility's [Communication
Settings] after writing [Controller Setting] of project data.
For details on the Utility, refer to the following manual.
➠
GOT2000 Series User's Manual (Utility)
(2) Precedence in communication settings
When settings are made by GT Designer3 or the Utility, the latest setting is effective.
(3) When changing Stage No. and Slot No.
Change these settings with the PLC CPU turned OFF, and then reapply the power to the PLC
CPU and GOT.
Failure to do so may generate a system alarm (No.487).
(4) Indirect specification of the servo axis No.
When the servo axis No. is specified to 100 to 115 in GT Designer3, the servo axis number
Item
Description
Range
Number of Stages
(Default: 1)
1 to 7
Slot No.
(Default: 0)
0 to 9
Monitor Speed
*3
Set the monitor speed of the GOT.
This setting is not valid in all systems. (Default: Normal)
High (Normal)
*1
/Middle/Low
*2
Timeout Time (Sec.)
Set the time period for a communication to time out. (Default: 12)
12 to 90
Servo axis switching GD device
head No.
Set the servo axis switching GD device head No. (Default: 10)
For details, refer to the following POINT.
➠
(4) Indirect specification of the servo axis No.
0 to 65520
Item
Description
Range
Number of Stages
(Default: 1)
1 to 7
Slot No.
(Default: 0)
0 to 7
Timeout Time (Sec.)
Set the time period for a communication to time out. (Default: 3)
3 to 90
Summary of Contents for GOT2000 Series
Page 2: ......
Page 84: ......
Page 432: ...6 58 6 6 Precautions ...
Page 578: ...9 54 9 6 Precautions ...
Page 726: ...12 84 12 5 Precautions ...
Page 756: ......
Page 822: ...14 66 14 4 Device Range that Can Be Set ...
Page 918: ...15 96 15 7 Precautions ...
Page 930: ...16 12 16 6 Precautions ...
Page 964: ......
Page 1002: ...19 38 19 7 Precautions ...
Page 1022: ...20 20 20 5 Precautions ...
Page 1023: ...MULTI CHANNEL FUNCTION 21 MULTI CHANNEL FUNCTION 21 1 ...
Page 1024: ......
Page 1054: ...21 30 21 5 Multi channel Function Check Sheet ...
Page 1055: ...FA TRANSPARENT FUNCTION 22 FA TRANSPARENT FUNCTION 22 1 ...
Page 1056: ......
Page 1223: ......