14.3 Ethernet Connection
14 - 51
INVERTER
C
O
NNE
CTION
14
14.3.3
Inverter side settings
For details of the inverter, refer to the manual of each series.
■1.
Connecting FREQROL-A800/F800-E series
(1) Communication settings
Make the communication settings of the inverter.
Be sure to perform the inverter reset after updating each parameter.
(a)
Communication port and corresponding parameters
(b)
Communication settings of inverter
Set the following parameters using the PU (parameter unit).
Do not change these parameters, even though they can be monitored from the GOT. If they are changed,
communication with the GOT is disabled.
GOT connection
destination
Parameters corresponding to inverter
Ethernet connector
Pr.79, Pr.340,Pr.342, Pr.414, Pr.502, Pr.549 to 551, Pr.779, Pr.1424 to 1429, Pr.1431 to 1432, Pr.1434 to 1455
Setting item
*1
Parameter
No.
Set value
Contents of setting
Operation mode switching
Pr.79
PU
connector
1
PU operation mode
RS-485
0
*3
External operation mode at power on
Communication startup
mode
Pr.340
PU
connector
0
*3
Refer to Pr.79 settings.
RS-485
1
Network operation mode.
Communication EEPROM
write selection
Pr.342
0
*3
Written to RAM and EEPROM
PLC function operation
*4
Pr.414
1, 2
Enabled with 1 and 2.
Stop mode selection at
communication error
Pr.502
0
*3
Please set to [0].
Protocol selection
Pr.549
0
*3
Please set to [0].
NET mode command
source selection
Pr.550
5
Please set to [5].
PU mode command source
selection
Pr.551
5
Operation frequency during
communication error
Pr.779
9999
*3
Please set to [9999].
Ethernet communication
network number
*2
Pr.1424
1 to 239
According to the GOT settings.
Ethernet communication
station number
*2
Pr.1425
1 to 120
Link speed and duplex
mode selection
Pr.1426
0
Please set to [0].
Ethernet function selection
1
*2
Pr.1427
5000 to 5002,
5006 to 5008
According to the GOT settings.
Ethernet function selection
2
Pr.1428
9999
Please set to [9999].
Ethernet function selection
3
Pr.1429
9999
Ethernet signal loss
detection function selection
Pr.1431
0
*3
Please set to [0].
Ethernet communication
check time interval
Pr.1432
9999
*3
Please set to [9999].
Summary of Contents for GOT2000 Series
Page 2: ......
Page 84: ......
Page 432: ...6 58 6 6 Precautions ...
Page 578: ...9 54 9 6 Precautions ...
Page 726: ...12 84 12 5 Precautions ...
Page 756: ......
Page 822: ...14 66 14 4 Device Range that Can Be Set ...
Page 918: ...15 96 15 7 Precautions ...
Page 930: ...16 12 16 6 Precautions ...
Page 964: ......
Page 1002: ...19 38 19 7 Precautions ...
Page 1022: ...20 20 20 5 Precautions ...
Page 1023: ...MULTI CHANNEL FUNCTION 21 MULTI CHANNEL FUNCTION 21 1 ...
Page 1024: ......
Page 1054: ...21 30 21 5 Multi channel Function Check Sheet ...
Page 1055: ...FA TRANSPARENT FUNCTION 22 FA TRANSPARENT FUNCTION 22 1 ...
Page 1056: ......
Page 1223: ......