18
(1)The LM ADAPTER is not completely
initialized.
(2)Setting on M-NET side is not properly
completed.
(3)If system controller is used together
LM ADAPTER is not registered to
system controller.
(4)The independent/interlocked
LOSSNAY of LM ADAPTER is not
set.
(5)L
ON
W
ORKS
®
network transmission
wire is not properly connected.
(6)The termination of L
ON
W
ORKS
®
network is not properly set.
(7) Binding of L
ON
W
ORKS
®
network is
not properly ended.
Refer to 2-(1).
Refer to 2-(2).
Refer to 2-(3).
Refer to 3-(4).
Refer to 4-(4).
Refer to 4-(5).
Refer to 4-(6).
Error content
Cause
Checking method and remedy
Independent/interl
ocked LOSSNAY
can not be
operated from the
LON side.
(1)The LM-ADAPTER is not completely
initialized.
(2)Setting on M-NET side is not properly
completed.
(3)If system controller is used together
LM ADAPTER is not registered to
system controller.
(4)L
ON
W
ORKS
®
network transmission
wire is not properly connected.
(5)The termination of L
ON
W
ORKS
®
network is not properly set.
(6) Binding of L
ON
W
ORKS
®
network is
not properly ended.
Refer to 2-(1).
Refer to 2-(2).
Refer to 2-(3).
Refer to 4-(4).
Refer to 4-(5).
Refer to 4-(6).
Air conditioner can
not be operated
from the LON side.
5
6
7
8
Prohibit local remote
controller operation
cannot be set from
the LON side.
Forced thermo OFF
cannot be set from
the LON side.
(1) Perform the LM ADAPTER’S prohibit
local remote controller operation
setting.
(1) Perform the LM ADAPTER’S forced
thermo OFF setting.
Turn on SW1-8 of LM ADAPTER, and reset the power
supply.
Turn on SW1-1 of LM ADAPTER, and reset the power
supply.