4
2-3 Connected Air Conditioning Equipment
2-4 L
ON
W
ORKS
®
Network Specifications
* The proper communication is not obtainable when communication intervals exceed its performance,
assure sufficeint intervals.
* ACK Service is recommended for the network service.
* Detailed specifications for the L
ON
W
ORKS
®
network can be found in “FT3120/FT3150 Smart Transceiver
Data Book” by Echelon Corporation.
Item
Description
Connected Equipment
Number of Units
LM ADAPTER can control 50 indoor units (including LOSSNAY)
Item
Description
FT3150-P20 (10MHz)
Neuron CHIP
FT-X1 (Free Topology 78kbps)
Network Transformer
Performance
2.5 inputs/second
Average communication capacity
50 inputs/second (for one second)
Peak communication capacity
CITY MULTI
LOSSNAY
OA Processing Units
A-control unit (Mr.Slim)
AK-control unit (Mr.Slim)
K-control unit
Room air conditioner (RAC)
Housing air conditioner (HAC)
Air To Water Booster unit / Air To Water HEX unit
Dedicated Outside Air System
S series
Y series
HP series
R2 series
WY series
WR2 series
HVRF series
Model
: Supported
*1 Functions are limited. For details on each function, please consult your dealer.
Function (Monitor/Operation)
(Requires an adapter)
*1
(Requires an adapter)