The New Remote Controller PZ-60DR-E enable simple control setting

Can Be Used With AG-150A Centralized Controller

Centralized Controller System

LOSSNAY independent

Interlocked with Air conditioners

Interlocked with City Multi

Interlocked with Mr.Slim

City Multi

M-NET transmission line

Mr.Slim

LOSSNAY

RX

5

LOSSNAY

RX

5

Slim-LOSSNAY connection cable

LOSSNAY remote
controller
PZ-60DR-E

LOSSNAY remote
controller
PZ-60DR-E
can be connected

LOSSNAY RX

5

(Max 15 unit)

PZ-52SF-E can be used insted of PZ-60DR-E, 
However, function is limited and connecting 
position is different.

The LOSSNAY remote controller (PZ-60DR-E, 
PZ-41SLB-E) can not be used with this system.

PZ-41SLB-E can be connected however function 
is limited.

Centralized controller
AG-150A

Power supply unit
(PAC-SC51KUA)

Outdoor unit

Network remote
controller

Mr.Slim
remote controller

LOSSNAY remote
controller
PZ-60DR-E

LOSSNAY remote
controller
PZ-60DR-E

Mr.Slim
outdoor unit

Mr.Slim
indoor unit

Network remote
controller

LOSSNAY 

RX

5

LOSSNAY 

RX

5

LOSSNAY 

RX

5

LOSSNAY 

RX

5

LOSSNAY remote
controller
PZ-60DR-E

LOSSNAY 

RX

5

Ext. signal source

LOSSNAY remote
controller
PZ-60DR-E

Interlocked with 
City Multi indoor units

Interlocked with 
Mr. Slim indoor units

LOSSNAY units only

Interlocked with 
external devices

Internet

Switching Hub

Hub

LAN 
(100BASE-TX) 

A Control

Central Control PC

(TG-2000A)

 *Ver. 5.50 or later

Remote 
Monitoring PC

Hub

DIDO Controller (PAC-YG66DCA)

General Equipment

Temp/Humidity sensor

Watt hour meter

AI Controller (PAC-YG63MCA)

PI Controller (PAC-YG60MCA)

Note : Use a security device such as a VPN router when connecting the  
           AG-150A to the Internet to prevent unauthorized access.

AG-150A / GB-50A

M-NET

M-NET

Service company
/Sales office

Mobile phone
of service person

Remote 
monitoring PC

M-NET

M-NET
adapter

AG -150A

Remote monitoring 
via a Web browser

Remote monitoring 
via a Web browser

VPN
Router

VPN
Router

Modem

Power supply unit

(PAC-SC51KUA)

Lights

Ventilation

Modem

Functions

Item 

Controllable unit

ON/OFF

Operation mode switching

Temperature setting

Fan speed setting

Air flow direction setting

Schedule operation

Permit / Prohibit

local operation

Indoor unit intake temperature

Error

Test run

Ventilation interlock

External input/output

                                                                                  

 

Description

Up to 50 units/groups.

Run and stop operation for the air conditioner units and general equipment.
(To operate general equipment, PAC-YG66DCA is required.)

Switches between Cool / Dry / Auto / Fan / Heat. (Group of LOSSNAY unit : automatic ventilation/
vent - heat interchange/ normal ventilation) depending on the air conditioner unit. 
Auto mode is for City Multi R2 and WR2 series only.

     Cool/Dry : 19    (67   ) - 30    (87   ) [14    (57   ) - 30    (87   )]

     Heat : 17    (63   ) - 28    (83   ) [17    (63   ) - 28    (83   )]

     Auto : 19    (67   ) - 28    (83   ) [17    (63   ) - 28    (83   )]

[   ] in case of using middle-temperature on PDFY, PEFY-VML/VMR/VMS/VMH-by setting  DipSW7-1 to ON. 
Yet, PEFY-P-VMH-E-F is excluded.

Models with 4 air flow speed settings: Hi/Mid-2/Mid-1/Low

Models with 3 air flow speed settings: Hi/Mid/Low

Models with 2 air flow speed settings: Hi/Low

Fan speed setting (including Auto) varies depending on the model.

Air flow direction angles, 4-angle or 5-angle Swing, Auto    (Louver cannot be set)

Weekly schedule can be set by groups based on daily operation pattern. 

Individually prohibit operation of each local remote control function 
(Start/Stop, Change operation mode, Set temperature, Reset filter).

Measures the intake temperature of the indoor unit only when the indoor unit is operating.

When an error is currently occurring on an air conditioner unit, the afflicted unit and the error code are displayed.

This operates air conditioner units in test run mode.

The ventilation unit (LOSSNAY) is able to automatically start its operation when operation of the interlocked indoor unit starts.

By using optional external input/output adaptor (PAC-YG10HA) you can set and monitor the following. 

      Input : By level signal : "Batch start/stop", "Batch emergency stop"

                 By pulse signal : "Batch start/stop", "Enable/disable local remote controller"

   Output : "Start/stop", "Error/Normal"

Operations 

Display

X
X

*NOTE: Operation and displayed content vary depending on the indoor unit model.

: Each block

System structure

Controllers are one of the most important and familiar devices in an air conditioning system. Not only does it control to provide 
optimum air environment but supports operations to minimize running costs and to preserve energy. Through studies and 
development, we've visualized a new system controller meeting needs with versatile options. 
With a new coloured touch panel, new functions, and continuation of all the current G-50A functions, AG-150A visualizes its 
functions from basic control to advanced operations and bringing an ultimate controller to reality. 

                            – Design your control 
                                  with our new centralized controller; AG -150A.  

Indoor unit

Indoor unit

: Each floor

: Each unit

: Collective

: Each group

: Not available

Control

Summary of Contents for Lossnay LGH-150RX5-E

Page 1: ...U TOKYO 100 8310 JAPAN http Global MitsubishiElectric com Y08 003 Nov 2008 MEE Specifications subject to change without notice C o n c e n t r a t i n g w h a t w e c a n d o m o r e e v e r a n d d e f i n i t e l y ENERGY RECOVERY VENTILATORS RX5 SERIES MODEL ...

Page 2: ...50 38 5kJ kg DA 33ºC 20 1g kg DA 63 84 6kJ kg DA 26ºC 10 5g kg DA 50 52 9kJ kg DA Energy recovery calculating equation Indoor supply air temperature ºC Indoor temperature ºC Outdoor temperature ºC _ Temp recovery efficiency Outdoor temperature ºC Calculation example 16ºC 20ºC _ 0ºC 80 0ºC Energy recovery calculating equation Indoor supply air temperature ºC Outdoor temperature ºC Indoor temperatur...

Page 3: ...uilding during the cooling season such as early morning or at night By pass ventilation will draw in the cooler outside air and reduce the cooling load on the system 2 Night purge By pass ventilation can be used to release hot air from inside the building that has accumulated in buildings a business district during the hot summer season 3 Office equipment room cooling During cold season fresh air ...

Page 4: ...er than the room temperature ventilation starts automatically The air conditioning load required to reach the set temperature the next morning is reduced At night the outside temperature drops When the room becomes sufficiently cool ventilation is stopped Hot air is discharged Example B Weekly Example A Hourly 8 00 9 00 12 00 13 00 17 00 19 00 22 00 low high low high low extra low new RX5 series w...

Page 5: ... units and general equipment To operate general equipment PAC YG66DCA is required Switches between Cool Dry Auto Fan Heat Group of LOSSNAY unit automatic ventilation vent heat interchange normal ventilation depending on the air conditioner unit Auto mode is for City Multi R2 and WR2 series only Cool Dry 19 67 30 87 14 57 30 87 Heat 17 63 28 83 17 63 28 83 Auto 19 67 28 83 17 63 28 83 in case of us...

Page 6: ...olyolefin EU F7 Standard filter High efficiency filter EA OA Lighting etc Replacement components for the standard air filter supplied with the LOSSNAY LGH main unit Model Applicable model PZ 25RF8 E PZ 35RF8 E PZ 50RF8 E PZ 65RF8 E PZ 80RF8 E PZ 100RF8 E LGH 15RX5 E LGH 25RX5 E LGH 35RX5 E LGH 50RX5 E LGH 65RX5 E LGH 80RX5 E LGH 150RX5 E 2sets LGH 100RX5 E LGH 200RX5 E 2sets Filter material Dimens...

Page 7: ... back for more Cleanliness is the key to an attractive atmos phere and restaurants devote significant effort to ensuring the premises are sanitary Sanitation and cleanliness how ever are not enough No matter how clean a restaurant may look if there are bothersome odors lingering in the air all those efforts go to waste and the restaurant s clean image is tarnished For these reasons we invite resta...

Page 8: ...a high Air volume L s O mmH 2 0 30 25 20 15 10 5 Pa m2 h 300 250 50 100 150 200 250 200 150 100 50 0 20m 10m 5m 15m 50Hz Single phase 240V Exchange efficiency External static pressure 50 60 70 80 90 100mm length dia pipe 10 20 30 40 50 60 70 0 High Unit mm LGH 15 to 100RX5 LGH 150 and 200RX5 LGH 15RX5 E Frequency Power source Ventilation mode Fan speed Current A Power consumption W Air volume Mode...

Page 9: ...where duct direction 63 63 65 65 Inspection opening Extra low Extra high Low Temperature exchange efficiency efficiency Cooling Enthalpy exchange efficiency Heating Enthalpy exchange 25 20 0 150 90 80 70 60 50 Exchange efficiency 50Hz Single phase 240V 30m 20m 10m External static pressure 5 10 15 Pa O 2 H m m 100 90 80 70 60 40 50 Air volume L s m2 h length pipe 40m dia 400 50 100 30 150 200 250 3...

Page 10: ...ore air filter High Position where duct direction Inspection opening 208 192 Extra low Temperature exchange efficiency Enthalpyexchange efficiency Heating Enthalpy exchange efficiency Cooling Extra high Low High Unit mm LGH 50RX5 E LGH 65RX5 E Ventilation mode Fan speed Current A Power consumption W Air volume Model External static pressure Temperature exchange efficiency Enthalpy exchange efficie...

Page 11: ...pection opening 258 242 Low efficiency Heating Enthalpy Temperature exchange efficiency Enthalpy exchange efficiency Cooling exchange Extra high Extra low High 50Hz Single phase 240V External static pressure m 2 H m O 10 20 Exchange efficiency 0 m2 h 350 50 100 150 200 250 300 250mm length pipe dia 50 60 70 80 90 Pa 40 30 50 0 500 100 200 300 400 1200 1000 800 600 400 200 0 100m 60m 20m 40m 80m Ai...

Page 12: ...se 240V Pa Enthalpy exchange efficiency Cooling efficiency Heating Enthalpy exchange Temperature exchange efficiency Low High Extra high 90 80 70 60 50 External static pressure Exchange efficiency 0 500 1000 1500 2000 2500 300 200 100 400 500 m2 h 0 700 600 500 400 300 200 100 Air volume L s 10 20 30 40 50 0 2 H m m O Unit mm LGH 150RX5 E LGH 200RX5 E Ventilation mode Fan speed Current A Power con...

Page 13: ... controller Max 2remote controllers installable cable 2nd LOSSNAY unit Up to max 15 units 1 LGH 150RX5 and 200RX5 Definition of Symbols M1 Motor for exhaust fan X10 X11 X12 Relay contact M2 Motor for supply fan X101 X102 X103 Relay Supply fan speed control C Capacitor X201 X202 X203 Relay Exhaust fan speed control GM Motor for By pass operation CN1 Connector Transformer primary LS Microswitch CN2 ...

Page 14: ...nt condensation from forming If it is expected that the ambient temperature around the place where the LOSSNAY unit is installed will be high during the summer air conditioning season it is recommended that the indoor ductwork be covered with insulation material 7 Inspection opening 450 450 or 600 600mm must be installed on the filter and LOSSNAY core removing side LOSSNAY model selection advices ...

Reviews: