Models:

Contents

Safety precautions ............................................. 1
Outline drawings ................................................ 2
Standard installation examples .......................... 3
Installation method ............................................. 3
Function settings .............................................. 10
Trial operation .................................................. 12

Lossnay Energy Recovery Ventilator

LGH-15RX

5

-E,

LGH-25RX

5

-E,

LGH-35RX

5

-E

LGH-50RX

5

-E,

LGH-65RX

5

-E,

LGH-80RX

5

-E

LGH-100RX

5

-E,

LGH-150RX

5

-E,

LGH-200RX

5

-E

Installation Instructions

(For use by dealer/contractor)

Models LGH-15RX

5

-E to LGH-100RX

5

-E

Models LGH-150RX

5

-E and LGH-200RX

5

-E

This product needs to be installed properly in order to ensure maximum functionality as well as safety.
Please make sure to read this installation manual before starting the installation.

Installation must be performed by a dealer or installation contractor. Please note that improper installation may cause malfunction or accident.

Separate booklet “Operating Instructions” is provided for the customer. The booklet and this manual must be handed over to the customer after completing the installation.

Safety precautions

The following signs indicate that death or serious injury may be caused by failure to heed the precautions described below.

Prohibited

WARNING

Do not modify or disassemble.

(It could cause fire, electric shock or injury.)

Do not

disassemble

Prohibition of use in

bath or shower room

Connect the

grounding wire.

The instructions

given must be

followed.

The Lossnay unit and remote controller should not be installed
where it is highly humid, like a bathroom, or other wet place.

(It could cause electric shock or power leakage.)

Connect the product properly to ground.

(Malfunctioning or power leaks can cause electrical shock.)

Use the specified power supply and voltage. 

(Use of incorrect power supply

or voltage could cause fire or electric shock.)

Select a place with sufficient strength and install the main unit securely.
 

(It could cause injury if it falls.)

Wiring work must be performed by qualified professionals, and be
implemented safely and securely in accordance with the engineering
standards and the extension wiring rules for electrical equipment.

(Poor connection or improper wiring work could cause electric shock or fire.)

Install a power supply isolator at the power supply side as per local electrical regulations.
All supply circuits must be disconnected before obtaining access to the terminal devices.
Use the specified cable size and connect the cables securely to prevent disconnection
when they are pulled.
 

(If there is a defect in the connection, there is a possibility of fire.)

Select an adequate place  for the opening to introduce outdoor air, where it will
not intake the exhaust fumes like combustion gas, or others, and there is no risk
of blockage. 

(Shortage of fresh air could put the room in a state of oxygen deficiency.)

A duct made of steel must be installed with care not to be connected
electrically with metals such as metal , wire , stainless steel plate, or others.

(It could cause fire when power leakage occurs.)

The instructions

given must be

followed.

Do not place a burning appliance in a place where it is exposed
directly to the air from the Lossnay unit.

(It could cause an accident as a result of incomplete combustion.)

Do not use at a place where it is exposed to high temperatures
(40˚C or higher), naked flames, or in environment with
combustible fumes.
 

(It could cause fire.)

Do not use in an environment such as a chemical factory, where
hazardous gases such as acidic gases, alkaline gases, organic
solvent fumes, paint fumes, or gases containing corrosive
components are generated.
 

(It could malfunction.)

Do not install this product in a place where it is exposed to
ultraviolet light. 

(UV may damage covering insulation.)

Put on gloves during installation. 

(It could cause injury.)

Make sure the power supply isolator is turned off on the power
distribution panel when Lossnay is not used for a long period of
time after the installation.
 

(It could cause electric shock, power

leakage, or fire as a result of deteriorated insulation.)

Always use the specified suspension bolts, nuts and washers or
correctly rated wire / chain hangers.
 

(Use of hardware with insufficient

strength could result in the product dropping.)

The outside ducts must be tilted at a gradient (1/30 or more) down
toward the outdoor louvres from Lossnay, and properly insulated.

(The entry of rain water may cause power leakage, fire, or damage to household property.)

The control box cover must be closed after the installation. 

(Dust

or humidity may cause power leakage or fire.)

When connecting external devices (electrically operated damper,
lamp, monitoring unit, etc.) using output signals of the Lossnay
unit, make sure to install safety equipment for the external devices.

(It could cause fire, damage, etc. without safety equipment.)

CAUTION

CAUTION

When using the product where it is exposed to high temperatures and humidity (40˚C or
higher, RH 80% or higher), or where fog occurs frequently, moisture is likely to condense
in the core, and may result in condensation build up in the unit. The product should not
be used under such conditions.

Outdoor air may enter the Lossnay owing to the pressure difference between indoor
and outdoor or external winds even when the product is not operated. It is recommended
to install an Electrically operated damper to block the outdoor air.

In a cold weather area, an area with strong external winds or where fog occurs frequently,
cold outdoor air, external winds or fog may be introduced into the product when its
operation is stopped. It is recommended to install 

an Electrically operated damper

.

When using the product in an environment where there is a window, or opening near
the outdoor louvre , where insects are likely to gather around the interior or exterior
light , take note that small insects may intrude into the product.

In a cold weather area, or others, dewing or freezing could occur on the main unit,
where the duct is connected, or other sections, depending on the conditions of outdoor
air and indoor temperature and moisture, even if they are within the range of operating
conditions. Make sure to confirm the operating conditions and other precautions, and
do not use the product if dewing or freezing is anticipated.

*Example of dewing condition – Outdoor air: -5˚C or lower, dew-point temperature at installation place: 10˚C or

higher (When the indoor temperature is 22˚C or higher with the relative humidity higher than 50%, or other)

Summary of Contents for Lossnay LGH-150RX5-E

Page 1: ...s a result of incomplete combustion Do not use at a place where it is exposed to high temperatures 40 C or higher naked flames or in environment with combustible fumes It could cause fire Do not use in an environment such as a chemical factory where hazardous gases such as acidic gases alkaline gases organic solvent fumes paint fumes or gases containing corrosive components are generated It could ...

Page 2: ...200 RX5 Model A B C D Weight kg LGH 150 RX5 1004 690 690 1045 105 LGH 200 RX5 1231 917 917 1272 118 Unit mm Accessory parts Duct connecting flanges x4 Mounting screws x16 Slim Lossnay connection cable gray two wires x1 Ceiling suspension fixture 4 15 x 30 oval SA supply air RA return air EA exhaust air outlet OA outside air intake Core air filter High Efficiency filter fan maintenance space Lossna...

Page 3: ...de air intake Supply air grille not included Except the 150 and 200 RX5 Remote controller optional parts EA exhaust air outlet OA outside air intake It can be installed by inverting the top and the bottom After installing the duct connecting flange remove the maintenance cover Turn the cover by 180 and then reinstall it Maintenance space Lossnay unit Inspection opening EA exhaust air outlet OA out...

Page 4: ...is recommended that the indoor ductwork be covered with insulation material Do not carry out the following types of duct construction Doing so could cause a drop in the air volume and generate abnormal noises 5 When changing the direction of the out door side duct EA OA Except for LGH 150 and 200 RX5 1 Removal of flange cover Unscrewing the flange cover mounting screws 4 pcs remove the flange cove...

Page 5: ...is product the wiring installation method will vary according to the design of the system Perform electrical installation to meet local electrical regulations Always use double insulated PVC cable for the transmission cables Wiring work must be performed by qualified professionals All supply circuits must be disconnected before obtaining access to the terminal devices M1 Motor for exhaust fan M2 M...

Page 6: ...onnector of control board 2 1 TM4 S B A TB5 M NET When the optional Remote Controller PZ 60DR E is used as the M NET System connect it to 1 2 of TM4 terminal block and connect M NET transmission wire to A B on TB5 terminal block 2nd remote controller Max 2 remote controllers installable 2 PZ 41SLB E and PZ 52SF E cannot be used when using PZ 60DR E M NET Transmission cable Shielded wire 2nd or lat...

Page 7: ...nnected to single input terminal is up to 4 wires for ø0 65 PVC wire or 0 3 mm2 stranded wire It is up to 2 wires for any other wires PZ 41SLB E cannot be used when MELANS centralized control of the Lossnay is used PZ 60DR E and PZ 41SLB E cannot be installed simultaneously 1 Connect the output signal cable from the external device to the input terminal block TM2 of the external controller CAUTION...

Page 8: ...3 3 and the negative side to 1 1 1 1 1 2 Confirm that the pulse input switch SW2 2 is set to OFF Set to OFF at time of shipment When the external device has a charged operating signal of 12 VDC or 24 VDC Connect the operating signal wire from the external device via the remote output to 1 and 2 on the external control input terminal block TM2 No polarity 1 Move the pulse input switch SW2 2 to the ...

Page 9: ...y Contactor rating DC 1 mA When connecting to the City Multi Lossnay remote controller PZ 52SF E or Mitsubishi Electric Air Conditioner Network System MELANS 10 Remote ON OFF adaptor Optional PAC SA88HA E When SW1 is ON fan speed of the Lossnay will be set to Low regardless of the remote control setting Use this in such a way that it ventilates at High fan speed normally and when the external sens...

Page 10: ...roller When interlocking with Mitsubishi Free Plan air conditioner Incase of PZ 60DR E Limit the total length of transmission wires no longer than 500 m Limit the wiring length between Lossnay and the power supply unit Optional or the outdoor unit no longer than 200 m M NET transmission cable Lossnay M NET transmission cable Power supply unit Lossnay MELANS M NET transmission cable Air conditioner...

Page 11: ...door OA air temperatures and automatically select the Lossnay ventilation or Bypass ventilation With this mode however priority is given to the Bypass ventilation This setting reflects to the night purge operation condition Bypass automatic ventilation priority setting 5 OFF ON 7 7 SW2 Operation When outdoor temperature OA is 28 C or higher within 24 hours then Bypass ventilation starts by the com...

Page 12: ...pply fan is stopped during defrosting of the air conditioner when Mr Slim or City Multi indoor unit is connected to a duct When the outdoor air is lower than 15 C stop the operation of exhaust fan OA stop operation at cold region Operation Exhaust fan operation factory setting Exhaust fan stop exhaust fan operation at Low speed at outdoor air lower than 15 C OFF ON 3 3 SW5 Settings for automatic r...

Page 13: ...the external device has come off of the external control input terminal Check in the case of multiple units whether the Main Sub selection switch on the Lossnay unit which is connected to the external control input terminal is set on the Master setting and check whether the Main Sub selection switch on other Lossnay units are set to Sub Check that the trial operation switch SW2 1 is set to off Cha...

Reviews: