background image

 

Removal of components 

 

 

Removing the front panel 

  Remove the screws at each side of the front panel.

 

② 

Pull down the front panel at this side.

 

③ 

Push the spring inward and remove from the slot at each side.

 

④ 

Draw out the front panel in the direction of the arrow. 

 The panel is suspended with wires that do not drop off. 

 
 
 

 
 
 
 
 
 
 
 
 
 

Removing the maintenance cover 

Turn the stopper 90 degrees and remove the maintenance cover.

 

 
Removing the air filters   

(at outside air intake and return air sides) 

 Remove air filters from the Lossnay core.

 

 

Cleaning the air filter 

 

Lightly tap with hand or use a vacuum cleaner to 
remove dust. 

 When they are soiled heavily, wash them by pushing down 

repeatedly in water or warm water (40

 or lower) containing 

neutral detergent. Dry them completely. 

 
 

 Never attempt to use hot water or squeeze to wash. (Air filters 

could be deformed and become unable to maintain the designed 
capacity.) 

 Be sure to install the air filters. 

 Care must be taken not to damage the surfaces of Lossnay core 

when removing or installing the air filters.

 

 

 

Cleaning the Lossnay core 

 

Remove dirt or dust from the surface using a vacuum 

cleaner. Lightly contact the nozzle of cleaner with 

long brush to make clean. 

 
 

 Do not splash the Lossnay core with water, hot water, chemicals, 

volatile solvent, or others. 

 Refrain from pressing hard on the Lossnay core with steel wire, 

screw driver, hard nozzle of cleaner, or the likes. 

 

 

 

Request 

Request 

English 

Prohibition of
washing with 
water 

Summary of Contents for Lossnay LGH-40ES-E

Page 1: ...g operation under such conditions could cause trouble electric shock fire or others Do not place a combustion equipment at a place where exposed directly to the wind from Lossnay It could cause accident as a result of incomplete combustion Do not place an object or sit on the main unit It could cause trouble electric shock fire or others Do not use at a place where exposed to high temperatures 40 ...

Page 2: ...it is in live condition Put on gloves during maintenance Otherwise it could cause injury Install parts securely after the maintsenance There is the risk of injury if parts drop off Frequency of cleaning Air filter Once or more per year Lossnay core Once or more per every 2 years Frequency should be increased depending on the extent of soiling Turn on the main power and conduct the following checks...

Page 3: ...d heavily wash them by pushing down repeatedly in water or warm water 40 or lower containing neutral detergent Dry them completely Never attempt to use hot water or squeeze to wash Air filters could be deformed and become unable to maintain the designed capacity Be sure to install the air filters Care must be taken not to damage the surfaces of Lossnay core when removing or installing the air filt...

Page 4: ...ntaining abrasive like cleanser When Malfunction is suspected Phenomenon Cause Remedy Power supply is not turned on Turn on the power supply Failure of ventilation Air filter or Lossnay core is clogged Make clean in accordance with the Maintenance When the trouble persists even after taking action as above consult your dealer After sales servicing Contact your dealer or nearby Mitsubishi repair se...

Reviews: