3. Terminology
●
Interlocked Lossnay
This is a Lossnay linked to City Multi, or Mr. Slim indoor units. This is a Lossnay that has been set to interlocked group set-
ting to receive signals and operate via indoor unit’s remote controller
→
indoor unit
→
Lossnay.
●
Non-interlocked Lossnay
This is a Lossnay that is not set to interlocked group setting with City Multi nor Mr. Slim indoor units. It operates using direct
operating signals from the Lossnay remote controller and/or centralised controller.
●
Ventilation Mode
This mode controls the Lossnay damper and permits selection of heat recovery (Heat ex.), by-pass or auto modes.
●
Delayed Operation
The Lossnay that has been set to interlocked group setting with the indoor unit will have its operation delayed for 30 minutes
after the operation of the indoor unit. When using PZ-41SLB-E, the time setting that can be set for delayed operation are 10,
20, 30, 40, 50 and 60 minutes.
●
External Control Input
This is an input signal for operating the Lossnay that has been sent from an external device. It is compatible with 12V-24V
DC or uncharged a-contact signal.
●
Operation Mode
This mode is used for selecting enabling/disabling of the on/off control signal from an external device and for setting inter-
locked operation of the external device and the Lossnay.
Please Refer to page 128 for details.
ON/OFF interlock:
Enables both “ON
→
OFF” and “OFF
→
ON” external signals.
ON interlock:
Enables “OFF
→
ON” external signal. Disables “ON
→
OFF” external signal.
OFF interlock:
Enables “ON
→
OFF” external signal. Disables “OFF
→
ON” external signal.
External priority:
Same as on/off interlock but the OFF signal from the remote controller is ignored when the
external control signal is on.
●
Setting Pulse Input
When the control signal from the external device outputs a pulse such as the one shown below, pulse input setting is per-
formed by the Lossnay. (Optional setting DIP switch 2-2 ON)
200 ms or more
●
Operation in Cold Areas
When the outdoor air is less than -10°C, continuous operation of the fan for drawing in supply air is cancelled, and intermit-
tent operation is started.
●
RA (Return Air)
This is the abbreviation for return air, which is the air drawn in from indoor.
●
OA (Outdoor Air)
This is the abbreviation for outdoor air, which is the air drawn in from outdoor.
(
Summary of Contents for Lossnay PZ-41SLB-E
Page 4: ...CHAPTER 1 Ventilation for Healthy Living Lossnay Unit ...
Page 17: ......
Page 18: ...CHAPTER 2 Lossnay Construction and Principle ...
Page 24: ...CHAPTER 3 General Technical Considerations ...
Page 41: ......
Page 42: ...CHAPTER 4 Characteristics ...
Page 56: ...53 CHAPTER 4 Characteristics ...
Page 57: ...54 CHAPTER 4 Characteristics ...
Page 59: ......
Page 60: ...CHAPTER 5 System Design Recommendations ...
Page 68: ...CHAPTER 6 Examples of Lossnay Applications ...
Page 83: ......
Page 84: ...CHAPTER 7 Installation Considerations ...
Page 88: ...CHAPTER 8 Filtering for Freshness ...
Page 96: ...CHAPTER 9 Service Life and Maintenance ...
Page 98: ...CHAPTER 10 Ventilation Standards in Each Country ...
Page 101: ......
Page 102: ...CHAPTER 11 Lossnay Q and A ...
Page 108: ...Lossnay Remote Controller ...
Page 109: ......
Page 197: ...MEMO ...
Page 198: ...Y04 002 Jul 2004 MEE ...