152
(2) Checklist of error codes displayed on the PZ-52SF-E, M-NET controllers, and LED
displays (Table 2-2)
6600
Error code
—
LED1
(green)
6
blinks
LED 2
(red)
Multiple
address error
«
There is another unit with the same
address setting.
«
Check the addresses of devices in
the system.
6607
6608
—
8
blinks
No ACK error
No answer
error (M-
NET com-
munication
error)
«
Power supply to Lossnay is not turned on.
«
Lossnay address was changed.
«
Multiple transmission cables have
been wired using multi core wires.
«
Transmission cable is not securely
connected.
«
The length of wiring of the transmission
cable is longer than specifications (longer
than maximum 200 m from the power sup-
ply unit, longer than 500 m between ends).
«
Check the power to the Lossnay.
«
Check the Lossnay address.
«
Wire the transmission cable away
from the other transmission cable.
«
Check the transmission cable con-
nection. (refer to page 165)
«
Check the length of the transmis-
sion cable wiring.
0900
—
—
Lossnay
trial opera-
tion
«
Trial operation switch on the Loss-
nay circuit board (SW 2-1 or SW 2-
3) is set to ON.
«
Check the trial operation switch.
(refer to page 169)
4116
2
blinks
—
Fan motor
operation
device error
«
Lossnay fan will not stop.
«
Replace the table.
3602
3
blinks
—
Damper
related
error
«
Damper board operation is not cor-
rect.
«
Connectors for the damper unit are
not correctly connected.
«
Remove the load and check or
move the damper board by hand.
«
Check the connection of the lead wires
connectors and the circuit connector.
5101
4
blinks
—
OA thermis-
tor related
error
«
Connectors for the thermistor are
not correctly connected.
«
Check the connection of the lead
wires connectors and the circuit
connector.
5102
5
blinks
—
RA thermis-
tor related
error
«
Connectors for the thermistor are
not correctly connected.
«
Check the connection of the lead
wires connectors and the circuit
connector.
6602
6603
6604
—
1 - 5
blinks
Communi-
cation cir-
cuit sec-
tion error
«
Error with transmission cable.
«
Controller where error originally
occurred is defective.
«
Lossnay board is defective.
«
Check transmission cable relations.
«
Check the controller where the error
occurred.
«
Replace the circuit board.
———
—
Lit
No M-NET
connection
information
«
Lossnay does not have Group set-
ting (registration) made.
«
Check the Lossnay address and con-
firm that the group setting is made.
(refer to page 179 or “15. Appendix”)
Filter blinking
—
—
Warning to clean air
filter by comulative
operation time
«
Interval for cleaning Lossnay air fil-
ter has elapsed.
«
After cleaning the air filter press the
“Filter” button on the remote con-
troller 2 times.
———
Lit
—
In delayed
start oper-
ation
«
Delayed start operation is set at the
function select switch (SW 5-1) on
the Lossnay circuit board.
«
There is no error.
———
LED6 (red)
off
No power
to M-NET
transmis-
sion cable
«
Power supply is not supplied to the
M-NET transmission cable.
«
Wiring length of the transmission cable
is from the power supply unit or the out-
door unit is longer than specification
(maximum extension 200 m).
«
Check the connection of the power
supply unit, outdoor unit and trans-
mission cable.
«
Check the length of the transmis-
sion cable wiring.
Symptom
Cause
Corrective action
*1 The letters “LC” that display with the error code show a Lossnay unit type, and the number in the third column shows the
address.
*2 Because the LGH-200RX type is loaded with 2 control circuit units, 1 Lossnay unit has 2 addresses. Check and perform
maintenance on the table related to the address set at the address switch (SA1, SA2).
Summary of Contents for Lossnay PZ-41SLB-E
Page 4: ...CHAPTER 1 Ventilation for Healthy Living Lossnay Unit ...
Page 17: ......
Page 18: ...CHAPTER 2 Lossnay Construction and Principle ...
Page 24: ...CHAPTER 3 General Technical Considerations ...
Page 41: ......
Page 42: ...CHAPTER 4 Characteristics ...
Page 56: ...53 CHAPTER 4 Characteristics ...
Page 57: ...54 CHAPTER 4 Characteristics ...
Page 59: ......
Page 60: ...CHAPTER 5 System Design Recommendations ...
Page 68: ...CHAPTER 6 Examples of Lossnay Applications ...
Page 83: ......
Page 84: ...CHAPTER 7 Installation Considerations ...
Page 88: ...CHAPTER 8 Filtering for Freshness ...
Page 96: ...CHAPTER 9 Service Life and Maintenance ...
Page 98: ...CHAPTER 10 Ventilation Standards in Each Country ...
Page 101: ......
Page 102: ...CHAPTER 11 Lossnay Q and A ...
Page 108: ...Lossnay Remote Controller ...
Page 109: ......
Page 197: ...MEMO ...
Page 198: ...Y04 002 Jul 2004 MEE ...