165
5. When switching High/Low speed external-
ly (when CO
2
sensor or other unit is con-
nected)
If a commercially available CO
2
sensor or other such unit is
used as shown in the drawing, connect by inserting Remote
ON/OFF Adaptor (PAC-SE55RA-E) (sold separately) to the
CN16 connector (for switching between High/Low).
* The LGH-200RX type are connected to the lower circuit
unit. (Main circuit board)
* Note that if the remote controller is connected to a CO
2
sensor, the actual high and low fan speeds may not match
on the remote controller.
●
To force high speed externally
When external switch is “ON” fan speed of the Lossnay will
be set to “High”.
Regardless of the remote control setting.
●
To force low speed externally
When external switch is “ON” fan speed of the Lossnay will
be set to “Low”.
Regardless of the remote control setting.
6. When connecting to the City Multi,
Lossnay M-NET remote controller (PZ-
52SF-E) or Mitsubishi Electric Air-
Conditioner Network System (MELANS)
* If centralised control is performed according the wire con-
nection shown in this section, the remote controller (PZ-
41SLB-E) cannot be used.
• One shieled wire is connected to the other shieled wire.
(Terminal connection)
Address setting is required. (Refer to function setting section.)
M-NET transmission cable: Connect any of the following --
City Multi indoor unit, Lossnay
remote controller (PZ-52SF-E)
or Mitsubishi Electric Air-
Conditioner Network System
(MELANS) - to the Lossnay.
Type:
(Shielded wire, CVVS/CPEVS)
Wire diameter:
1.25 mm
2
to 2.0 mm
2
• Securely connect the M-NET transmission cable to
A
and
B
on the transmission cable input terminal block (TB5).
(Non-Polar)
CN16
CO
2
sensor, etc.
(Closed when there is
an increase in CO
2
)
Switch: High
operation switch
(When closed,
high operation)
Remote ON/OFF
adaptor (sold separately
PAC-SE55RA-E)
Not used. Insulate
completely.
Lossnay controller
circuit unit
High/Low
switching
Orange 1
Switch
Red 2
Brown 3
Wiring length up to a maximum
of 10 m
CN16
CO
2
sensor, etc.
(Closed when there is
an increase in CO
2
)
Switch: Low
operation switch
(When closed,
low operation)
Remote ON/OFF
adaptor (sold separately
PAC-SE55RA-E)
Not used. Insulate
completely.
Lossnay controller
circuit unit
High/Low
switching
Orange 1
Switch
Red 2
Brown 3
Wiring length up to a maximum
of 10 m
A
B
S
A
6
5
B
S
Round terminal
M-NET transmission cable input terminal block
M-NET transmission cable
LGH-50 and 100RX
types
TB5
LGH-200RX type
TB5
Shielded wire
Summary of Contents for Lossnay PZ-41SLB-E
Page 4: ...CHAPTER 1 Ventilation for Healthy Living Lossnay Unit ...
Page 17: ......
Page 18: ...CHAPTER 2 Lossnay Construction and Principle ...
Page 24: ...CHAPTER 3 General Technical Considerations ...
Page 41: ......
Page 42: ...CHAPTER 4 Characteristics ...
Page 56: ...53 CHAPTER 4 Characteristics ...
Page 57: ...54 CHAPTER 4 Characteristics ...
Page 59: ......
Page 60: ...CHAPTER 5 System Design Recommendations ...
Page 68: ...CHAPTER 6 Examples of Lossnay Applications ...
Page 83: ......
Page 84: ...CHAPTER 7 Installation Considerations ...
Page 88: ...CHAPTER 8 Filtering for Freshness ...
Page 96: ...CHAPTER 9 Service Life and Maintenance ...
Page 98: ...CHAPTER 10 Ventilation Standards in Each Country ...
Page 101: ......
Page 102: ...CHAPTER 11 Lossnay Q and A ...
Page 108: ...Lossnay Remote Controller ...
Page 109: ......
Page 197: ...MEMO ...
Page 198: ...Y04 002 Jul 2004 MEE ...