167
OFF
ON
Mode
Operation
6
OFF
Stopping and operation is performed according to settings
SW2
(Factory setting)
of SW5-4 when the power is on.
6
ON
Operation possible by turning power on and off.
OFF
ON
Mode
SW2
2
No pulse input (factory setting)
2
Pulse input
OFF
ON
Operation
SW5
3
Exhaust fan operation (factory setting)
3
Exhaust fan stopped
OFF
ON
Mode
SW5
1
No operation delay (factory setting)
1
Operation delay of 30 minutes
* This function is invalid with in 2 hours’ restart
OFF
ON
Mode
2
Corresponds to operation mode output (TM3
9
,
0
) exhaust fan (factory setting)
SW5
Corresponds to operation mode output (TM3
9
,
0
) supply fan
2
(The operation monitor output is off when the supply fan is stopped for operation in
cold regions or during the City Multi or Mr. Slim defrosting.)
OFF
ON
Mode
Operation
4
Normal
Switches High/Low by operation of the fan speed from
5
(Factory setting)
remote control.
SW2
4
Fixed at high mode
Normally operated at high speed.
5
4
Fixed at low mode
Normally operated at low speed.
5
12.3.2 Switching function selection switches (SW-2 and 5)
Perform the necessary function settings using the function selection switches (SW-2 and 5).
●
The setting can be changed at any time.
●
On the LGH-200RX type, set both the upper and lower circuit boards similarly.
1. Settings for pulse input
Set as shown when connecting the pulse signal equipment from a building maintenance system to an external input.
2. Setting for selection of fan speed method
Set when operation is fixed at high speed or low speed operation. There are three modes that can be set.
3. Power supply ON/OFF function (cannot be set when PZ-41SLB-E is used)
Set can be switch when operation and stopping is performed by turning the power supply (208-230 V) for the Lossnay on
and off.
4. Settings for delay (of operation at start-up of heating or cooling)
This is the mode for delaying the operation of the Lossnay for 30 minutes when the City Multi or Mr. Slim is started and when
a external device is started. (If the PZ-41SLB-E is used, set it at the remote control. Refer to page 168.)
6. Stopping exhaust fan when defrosting air conditioner
Sets the operation of the exhaust fan (when the air supply fan is stopped) during defrosting of the air conditioner when Mr.
Slim or City Multi indoor unit is connected to a duct.
5. Supply air fan monitor
Summary of Contents for Lossnay PZ-41SLB-E
Page 4: ...CHAPTER 1 Ventilation for Healthy Living Lossnay Unit ...
Page 17: ......
Page 18: ...CHAPTER 2 Lossnay Construction and Principle ...
Page 24: ...CHAPTER 3 General Technical Considerations ...
Page 41: ......
Page 42: ...CHAPTER 4 Characteristics ...
Page 56: ...53 CHAPTER 4 Characteristics ...
Page 57: ...54 CHAPTER 4 Characteristics ...
Page 59: ......
Page 60: ...CHAPTER 5 System Design Recommendations ...
Page 68: ...CHAPTER 6 Examples of Lossnay Applications ...
Page 83: ......
Page 84: ...CHAPTER 7 Installation Considerations ...
Page 88: ...CHAPTER 8 Filtering for Freshness ...
Page 96: ...CHAPTER 9 Service Life and Maintenance ...
Page 98: ...CHAPTER 10 Ventilation Standards in Each Country ...
Page 101: ......
Page 102: ...CHAPTER 11 Lossnay Q and A ...
Page 108: ...Lossnay Remote Controller ...
Page 109: ......
Page 197: ...MEMO ...
Page 198: ...Y04 002 Jul 2004 MEE ...