Room Environment Standard Values
If a central air quality management system or mechanical
ventilation equipment is installed, comply with the standard target
values shown in the table below.
Central air quality management system ventilation capacity and
characteristics
Effective ventilation capacity V 20Af/N (m
3
)
Af: floor space (m
2
), N: floor space occupied by one person
Characteristics: Generally satisfy the table below.
For general ventilation, the effective ventilation area opening is
at least 1/20 of the floor space and the ventilation equipment
installed gives a CO density of 50 ppm and CO
2
density of 5,000
ppm or less. If a central air quality management system or
mechanical ventilation equipment is installed, comply with the
standard target values shown in the table below.
96
CHAPTER 10
●
Ventilation Standards in Each Country
1. Ventilation Standards in Each Country
1. Japan
Table Summary of Laws Related to Ventilation
Item
Related Laws
Law for Maintenance of
Sanitation in Buildings
The Building Standard Law of
Japan
Industrial Safety and Health
Act
Acceptable Range
Buildings of at least 3,000 m
2
(for
schools, at least 8,000 m
2
)
Buildings with requirements for
ventilation equipment
1) windowless rooms.
2) rooms in theaters, movie
theaters, assembly halls, etc.
3) kitchens, bathrooms, etc.
Rooms with equipment or devices
using fire.
Offices where workers work.
(Office sanitation regulated
standards)
Impurity volume of
less than 0.15 mg per 1 m
3
of
floating particles
air
Less than 10 ppm. (Less than 20
CO rate
ppm when outside supply air has
a CO rate of more than 10 ppm.)
CO
2
rate
Less than 1,000 ppm.
1) Between 17°C and 28°C
2) When making the room
Temperature
temperature cooler than the
outside temperature, do not
make the difference too great.
Relative humidity
40% - 70%
Ventilation
less than 0.5 m/sec
Impurity volume of
less than 0.15 mg per 1 m
3
of
floating particles
air
CO rate
Less than 10 ppm.
CO
2
rate
Less than 1,000 ppm.
1) Between 17°C and 28°C
2) When making the room
Temperature
temperature cooler than the
outside temperature, do not
make the difference too great.
Relative humidity
40% - 70%
Ventilation
less than 0.5 m/sec
Impurity volume of
Air (1 atmospheric pressure, 25°C)
floating particles
less than 0.15 mg per 1 m
3
of air
Less than 10 ppm. (Less than 20 ppm
CO rate
when outside supply air has a CO
rate of more than 10 ppm.)
CO
2
rate
Less than 1,000 ppm.
Air speed in room is less than
Air flow in room
0.5 m/s, and air taken into the room
does not blow directly on or reach
specific workers.
Heat and humidity
Heat between 17°C - 28°C
conditions
Relative humidity 40% - 70%
Summary of Contents for Lossnay PZ-41SLB-E
Page 4: ...CHAPTER 1 Ventilation for Healthy Living Lossnay Unit ...
Page 17: ......
Page 18: ...CHAPTER 2 Lossnay Construction and Principle ...
Page 24: ...CHAPTER 3 General Technical Considerations ...
Page 41: ......
Page 42: ...CHAPTER 4 Characteristics ...
Page 56: ...53 CHAPTER 4 Characteristics ...
Page 57: ...54 CHAPTER 4 Characteristics ...
Page 59: ......
Page 60: ...CHAPTER 5 System Design Recommendations ...
Page 68: ...CHAPTER 6 Examples of Lossnay Applications ...
Page 83: ......
Page 84: ...CHAPTER 7 Installation Considerations ...
Page 88: ...CHAPTER 8 Filtering for Freshness ...
Page 96: ...CHAPTER 9 Service Life and Maintenance ...
Page 98: ...CHAPTER 10 Ventilation Standards in Each Country ...
Page 101: ......
Page 102: ...CHAPTER 11 Lossnay Q and A ...
Page 108: ...Lossnay Remote Controller ...
Page 109: ......
Page 197: ...MEMO ...
Page 198: ...Y04 002 Jul 2004 MEE ...