14.2 Installing the Lossnay M-NET Remote Controller

14.2.1 Mount the switch box.

1. Install the switch box (purchased separately) as explained below. 

Note:

Be sure to install the switch box with the clearance shown in the illustration at
the left. (Check the space between the unit and any projections, such as a
stud.)

Leave a space of 120 mm or more below the Lossnay M-NET remote controller
so that a screwdriver can be used.

2. Purchase the thin copper wiring conduit, lock nuts and bushings separately. 

1. Pull out approximately 80 mm of cable from the wall and remove the insulation

at the end.

2. Use putty to seal the cable hole in order to prevent insects from damaging the

wiring and to prevent condensation on the Lossnay M-NET remote controller
circuit board.  If this hole is not sealed well, the Lossnay M-NET remote con-
troller circuit board  may be damaged.

3. Connect the cable to the terminal board at the bottom rear of the Lossnay M-

NET remote controller unit.

The cable does not have polarity.

When connecting stranded cable, hold down the tab on the terminal board
while inserting the cable. 

The cable connects to the main terminal board when it is inserted into the bot-
tom terminal.

When disconnecting the cable, hold down the tab while pulling out the cable.

After inserting the cable, slightly tug on it to check that it does not easily dis-
connect.  If the cable is not securely connected, a short-circuit or malfunction
may occur.

4. Remove the Lossnay M-NET remote controller cover using a standard screw-

driver.  Attach the Lossnay M-NET remote controller unit to the switch box
using the two enclosed cross-recessed pan head screws. Use a standard
screwdriver with a blade that is 4 mm or wider to remove the cover.

CAUTION:

Forcing off the cover using a screwdriver that is less than 4 mm wide may
result in damage to the equipment or injuries.

Attach the Lossnay M-NET remote controller to a level surface.  Do not over-
tighten the screws.  Tight screws could damage or deform the case.

Switch box

Outline of Lossnay
remote controller

Projecting
object such as
a stud

40 mm or more

11

10

80

Leading

wire

Insula-

tion

Sheath

Wall

Cable

Seal with putty

One switch box

(with cover)

Wiring plpe

Units : mm

Button:
Press here.

Insert the cable.

Lossnay M-NET remote 
controller cover

14.2.2 Install the Lossnay M-NET Remote Controller.

Summary of Contents for Lossnay

Page 1: ......

Page 2: ...ɶɬɪɚ ɂɧɞɢɤɚɰɢɹ ɪɚɛɨɬɵ Ƚɨɪɢɬ ɩɪɢ ɧɨɪɦɚɥɶɧɨɣ ɪɚɛɨɬɟ Ɇɢɝɚɟɬ ɩɪɢ ɧɟɢɫɩɪɚɜɧɨɫɬɢ Ɋɟɠɢɦ ɪɚɛɨɬɵ ɉɨɤɚɡɵɜɚɟɬ ɪɟɠɢɦ ɪɚɛɨɬɵ Ɋɟɤɭɩɟɪɚɬɨɪ 7 Ȼɚɣɩɚɫɫ 3 66 Ⱥɜɬɨɦɚɬɢɱɟɫɤɢ Ɋɟɤɭɩɟɪ Ȼɚɣɩɚɫɫ ɉɢɬɚɧɢɟ ɉɨɤɚɡɵɜɚɟɬ ɧɚɥɢɱɢɟ ɩɢɬɚɧɢɹ ɧɚ ɩɭɥɶɬɟ ɉɪɨɜɟɪɤɚ Ƚɨɪɢɬ ɫɨɜɦɟɫɬɧɨ ɫ ɧɟɢɫɩɪɚɜɧɨɫɬɶɸ ʋ ɛɥɨɤɚ ɰɢɮɪɵ ɨɲɢɛɤɚ ɰɢɮɪɵ ȼɪɟɦɹ ɡɚɞɟɪɠɤɢ ɉɨɤɚɡɵɜɚɟɬ ɜɪɟɦɹ ɡɚɞɟɪɠɤɢ ɍɫɬɚɧɨɜɤɚ ɡɚɞɟɪɠɤɢ 6 77 1 ɦɢɧ ɡɚɞɟɪɠɤɚ ȼɨ ɜɪɟɦɹ ɪɟɠɢɦɚ ɡɚɞɟɪɠɤɢ ɦɢɧ ɡɚɞɟɪɠɤɚ...

Page 3: ...ɢ ɜɟɧɬɢɥɹɬɨɪɚ ɢ ɭɫɬɚɧɨɜɢɬɟ ɜɵɫɨɤɭɸ LJK ɢɥɢ ɧɢɡɤɭɸ RZ ɫɤɨɪɨɫɬɶ ɇɚɠɦɢɬɟ 21 2 Ʌɚɦɩɚ ɢɧɞɢɤɚɰɢɢ ɪɚɛɨɬɵ ɩɨɝɚɫɧɟɬ ɉɪɢɦɟɪ ɪɟɠɢɦ ɛɚɣɩɚɫɫ ɉɪɢɦɟɪ ɧɢɡɤɚɹ ɫɤɨɪɨɫɬɶ ɂɧɞɢɤɚɰɢɹ ɪɚɛɨɬɵ ɂɧɞɢɤɚɰɢɹ ɪɚɛɨɬɵ ȼɪɟɦɹ ɡɚɞɟɪɠɤɢ Ɉɩɪɟɞɟɥɹɟɬ ɡɚɞɟɪɠɤɭ ɜɤɥɸɱɟɧɢɹ Ʌɨɫɫɧɟɣ ɩɨɫɥɟ ɩɨɞɚɱɢ ɜɧɟɲɧɟɝɨ ɫɢɝɧɚɥɚ ɭɩɪɚɜɥɟɧɢɹ ɋɜɹɡɚɧɧɵɣ ɪɟɠɢɦ ɍɫɬɚɧɚɜɥɢɜɚɟɬɫɹ ɱɬɨɛɵ ɡɚɞɚɬɶ ɩɨɪɹɞɨɤ ɜɤɥɸɱɟɧɢɹ Ʌɨɫɫɧɟɣ ɨɬ ɜɧɟɲɧɟɝɨ ɫɢɝɧɚɥɚ ɧɚɩɪɢɦɟɪ ɨɬ ɫɢɫɬɟɦɵ ɭɩɪɚɜɥɟɧɢɹ...

Page 4: ...ɬɤɢ ɩɭɥɶɬɚ ɪɚɫɬɜɨɪɢɬɟɥɢ ɛɟɧɡɢɧ ɢ ɩɪ Ⱦɢɫɩɥɟɣ Ⱦɟɣɫɬɜɢɹ ɇɚɠɦɢɬɟ ɤɧɨɩɤɭ LOWHU ɞɜɚ ɪɚɡɚ ɩɨɞɪɹɞ ɂɧɞɢɤɚɰɢɹ ɩɨɝɚɫɧɟɬ ɋɟɪɜɢɫɧɨɟ ɨɛɫɥɭɠɢɜɚɧɢɟ ȿɫɥɢ ɧɚ ɞɢɫɩɥɟɟ ɩɨɹɜɢɬɶɫɹ ɨɞɧɨ ɢɡ ɧɢɠɟɩɟɪɟɱɢɫɥɟɧɧɵɯ ɱɢɫɟɥ ɩɪɢɝɥɚɫɢɬɟ ɫɟɪɜɢɫɧɭɸ ɫɥɭɠɛɭ 7 5 ɇɚɠɚɬɶ ɞɜɚɠɞɵ 7 5 Ⱦɟɣɫɬɜɢɹ ɩɪɢ ɦɢɝɚɧɢɢ ɢɧɞɢɤɚɰɢɢ ɡɚɝɪɹɡɧɟɧɢɹ ɮɢɥɶɬɪɚ ȼɤɥ ɜɵɤɥ ɫ ɜɨɡɦɨɠɧɨɫɬɶɸ ɪɚɛɨɬɵ ɨɬ ɩɭɥɶɬɚ Ʌɨɫɫɧɟɣ Ʉɨɝɞɚ ɜɧɟɲɧɟɟ ɭɫɬɪɨɣɫɬɜɨ ɜɤɥɸɱɚɟɬɫɹ Ʌɨɫɫɧɟɣ ɬɨɠɟ ɜɤɥɸɱɚɟɬɫɹ ...

Page 5: ...ɟ ɨɬɜ Ⱦɢɫɩɥɟɣ ȼɵɛɨɪ ɪɟɠɢɦɚ Ʉɧɨɩɤɚ ȼɄɅ ȼɕɄɅ Ʉɪɵɲɤɚ ɋɛɪɨɫ ɢɧɞɢɤɚɰɢɢ Ɏɢɥɶɬɪ Ʉɥɟɦɦɵ ɂɧɞɢɤɚɬɨɪ ɪɚɛɨɬɵ Ɂɚɞɟɪɠɤɚ ɜɤɥ Ⱥɤɫɟɫɫɭɚɪɵ ɒɭɪɭɩɵ ȿɞ ɢɡɦ ɦɦ Ʉɚɛɟɥɶ ɍɫɬɚɧɨɜɢɬɟ ɩɭɥɶɬ ɧɚ ɫɬɟɧɟ ɛɟɡ ɩɟɪɟɞɧɟɣ ɩɚɧɟɥɢ ɉɪɨɛɪɨɫɶɬɟ ɤɚɛɟɥɶ ɞɨ ɩɭɥɶɬɚ ɉɨɞɤɥɸɱɢɬɟ ɫɢɝɧɚɥɶɧɭɸ ɥɢɧɢɸ ɤ Ʌɨɫɫɧɟɣ ɢ ɩɭɥɶɬɭ ɯ ɠɢɥɶɧɵɣ ɤɚɛɟɥɶ ɬɢɩ ɉȼɋ ɨɬ ɞɨ ɦɦð ɉɪɢɦ ɉɟɪɟɞ ɩɨɞɤɥɸɱɟɧɢɟɦ ɫɢɝɧɚɥɶɧɨɝɨ ɤɚɛɟɥɹ ɭɛɟɞɢɬɟɫɶ ɱɬɨ ɧɚ Ʌɨɫɫɧɟɣ ɧɟ ɩɨɞɚɧɨ ɩɢɬɚɧɢɟ ɋɧɹɬɢɟ ɩɟɪɟɞɧ...

Page 6: ... ĺ ĺ ĺ ĺ PLQXWHV Ĺ ɡɚɜɨɞɫɤɚɹ ɭɫɬɚɜɤɚ ȿɫɥɢ ɤɧɨɩɤɭ ɧɟ ɧɚɠɢɦɚɸɬ ɛɨɥɟɟ ɫɟɤ ɭɫɬɚɧɚɜɥɢɜɚɟɬɫɹ ɬɟɤɭɳɟɟ ɡɧɚɱɟɧɢɟ ɢ ɩɭɥɶɬ ɜɵɯɨɞɢɬ ɢɡ ɪɟɠɢɦɚ Ɉɛɪɚɬɢɬɟ ɜɧɢɦɚɧɢɟ ɱɬɨ ɟɫɥɢ ɫɜɹɡɚɧɧɵɣ ɪɟɠɢɦ Ʌɨɫɫɧɟɣ ɨɬɤɥɸɱɟɧ ɞɚɧɧɚɹ ɮɭɧɤɰɢɹ ɧɟ ɪɚɛɨɬɚɟɬ ɍɫɬɚɧɨɜɤɚ ɫɜɹɡɚɧɧɨɝɨ ɪɟɠɢɦɚ ɋɜɹɡɚɧɧɵɣ ɪɟɠɢɦ ɢɫɩɨɥɶɡɭɟɬɫɹ ɞɥɹ ɭɩɪɚɜɥɟɧɢɹ Ʌɨɫɫɧɟɣ ɨɬ ɜɧɟɲɧɟɝɨ ɭɫɬɪɨɣɫɬɜɚ Ⱦɥɹ ɭɫɬɚɧɨɜɤɢ ɫɜɹɡɚɧɧɨɝɨ ɪɟɠɢɦɚ ɧɚɠɦɢɬɟ ɢ ɭɞɟɪɠɢɜɚɣɬɟ ɤɧɨɩɤɭ ɞɥɹ ɜɯɨɞɚ ɜ ɪɟɠɢɦ Ɂ...

Page 7: ...ɶɧɨɫɬɶɸ ɞɨ ɫɟɤ Ɍɚɛɥɢɰɚ ɧɟɢɫɩɪɚɜɧɨɫɬɟɣ ɤɨɞ ɨɲɢɛɤɢ ɦɢɝɚɟɬ ɧɚ ɩɭɥɶɬɟ ɭɩɪɚɜɥɟɧɢɹ ɉɪɢɱɢɧɚ 6 ɜɤɥɸɱɟɧ ɉɪɢ ɭɩɪɚɜɥɟɧɢɢ ɨɬ ɞɜɭɯ ɩɭɥɶɬɨɜ ɧɟ ɭɫɬɚɧɨɜɥɟɧ ɨɫɧɨɜɧɨɣ ɢ ɞɨɩɨɥɧɢɬɟɥɶɧɵɣ ɩɭɥɶɬ ɉɪɢ ɭɩɪɚɜɥɟɧɢɢ ɨɬ ɞɜɭɯ ɩɭɥɶɬɨɜ ɨɞɢɧ ɢɡ ɩɭɥɶɬɨɜ ɧɟ ɩɨɞɤɥɸɱɟɧ ɉɪɢ ɭɩɪɚɜɥɟɧɢɢ ɨɬ ɞɜɭɯ ɩɭɥɶɬɨɜ ɧɢ ɨɞɢɧ ɩɭɥɶɬ ɧɟ ɡɚɩɭɫɬɢɥɫɹ ɚɜɬɨɦɚɬɢɱɟɫɤɢ ɩɪɢ ɩɨɞɚɱɟ ɩɢɬɚɧɢɹ ɂɫɩɨɥɶɡɭɟɬɫɹ ɨɞɢɧ ɦɧɨɝɨɠɢɥɶɧɵɣ ɤɚɛɟɥɶ ɜɦɟɫɬɨ ɞɜɭɯ ɨɬɞɟɥɶɧɵɯ ɞɥɹ ɤɚɠɞɨɝɨ ɩɭɥɶ...

Page 8: ...annot perform the function for the button that has been pressed This display flashes concurrently with the display of the unavailable function ON OFF Button Switches between run and stop The lamp on the button stays lit during operation Fan Speed Adjustment Button Used to select the fan speed of either Low or High FILTER Button Press two times to reset the filter sign display HEAT EX BY PASS AUTO ...

Page 9: ...nal board while inserting the cable The cable connects to the main terminal board when it is inserted into the bot tom terminal When disconnecting the cable hold down the tab while pulling out the cable After inserting the cable slightly tug on it to check that it does not easily dis connect If the cable is not securely connected a short circuit or malfunction may occur 4 Remove the Lossnay M NET ...

Page 10: ... a multi unit system Set the address according to its position in the system In addition refer to page 59 for more information concering the setting of the addresses 6 After setting the Lossnay M NET remote controller address attach the Lossnay M NET remote controller cover When attaching the Lossnay M NET remote controller cover set the top of the cover onto the two top hooks and then push in the...

Page 11: ...y M NET remote controller After the button is pressed once the Lossnay M NET remote controller address and then the Lossnay unit address is displayed Afterwards each press of the button increase the Lossnay unit address by 1 as shown below Holding down the button changes the address more quickly 101 001 002 098 099 Set Lossnay M NET remote controller address Flashes 4 When the address of the Lossn...

Page 12: ...eted to delete the regis tration of the Lossnay unit that is currently displayed FILTER When the display appears as shown above hold down ON OFF for 2 seconds each time If the registration is deleted correctly appears in the display If the registration is not deleted correctly flashes in the display Check that the select ed Lossnay unit addresses and the wiring are correct Note In the case of LGH ...

Reviews: