30
MITSUBISHI ELECTRIC
/ Y SERIES
PUMY-SP
Y SERIES -
DC Inverter/Heat Pump
SIZE
MODEL
DIAMETER
EXTERNAL PIPING
REFRIGERANT CHARGE
BREAKER
Liquid mm
(inches)
Gas mm
(inches)
Max
Height
Max
Lenght*
Max
Pipe Bends
Precharge
Kg*
Precharge
lenght
mt.
Additional
charge
g/mt
tonCO
2
eq
precharge*
tonCO
2
eq
max charge*
112
PUMY-SP
9,52 (3/8")
15,88 (5/8")
TAB.
3,50
0
TAB.
7,31
26,10
32 A / 16 A
125
3,50
7,31
26,10
32 A / 16 A
140
3,50
7,31
26,10
32 A / 16 A
Refrigerant piping diameter in section from
branch box to indoor unit
LIQUID LINE
GAS LINE
9,52 (3/8")
15,88 (5/8")
Refrigerant piping diameter in section from
branch box to branch box
LIQUID PIPES
SECTION
6,35 (1/4’’)
meters x 19 g/m
LIQUID PIPES
SECTION
9,52 (3/8’’)
meters x 50 g/m
+
+
INDOOR CONNECTED
CONNECTED
TOTAL POWER
AMOUNT OF REFRIGERANT
TO ADD
up to 8 kW
1,5 kg
8,1 kW to 16,0 kW
2,5 kg
over 16,1 kW
3,0 kg
ATTACCHI
PAC-MK53BC
PAC-MK33BC
Unit A
Liquid
6,35 (1/4”)
6,35 (1/4”)
Gas
9,52 (3/8”)
9,52 (3/8”)
Unit B
Liquid
6,35 (1/4”)
6,35 (1/4”)
Gas
9,52 (3/8”)
9,52 (3/8”)
Unit C
Liquid
6,35 (1/4”)
6,35 (1/4”)
Gas
9,52 (3/8”)
9,52 (3/8”)
Unit D
Liquid
6,35 (1/4”)
-
Gas
9,52 (3/8”)
-
Unit E
Liquid
6,35 (1/4”)
-
Gas
12,7 (1/2”)
-
*Pipes diameter have to coincide with the indoor units pipes diameter.
Any reduction will be made on the Branch Box.
Branch box connection section*
R410A
INDOOR UNIT
SERIES
MODEL
NUMBER
A
LIQUID PIPE
B
GAS PIPE
M series or
S series
15 to 42
Ø6.35
Ø9.52
50
Ø6.35
Ø12.7
60
Ø6.35
Ø15.88
71
Ø9.52
Ø15.88
P series
35,50
Ø6.35
Ø12.7
60 to 100
Ø9.52
Ø15.88
Summary of Contents for M-SERIES
Page 1: ...Practical installation guide DX ...
Page 2: ......
Page 3: ......
Page 5: ...3 ...
Page 37: ...35 ...
Page 39: ...37 MITSUBISHI ELECTRIC COMMERCIAL ...
Page 49: ...47 ...
Page 61: ...59 MITSUBISHI ELECTRIC REPLACE TECHNOLOGY ...
Page 75: ...73 MITSUBISHI ELECTRIC REPLACE TECHNOLOGY COMMERCIALE ...
Page 76: ...74 Ventilation ...
Page 77: ...75 MITSUBISHI ELECTRIC VENTILATION ...
Page 111: ...109 ...
Page 118: ......
Page 119: ......