46
SIZE
MODEL
DIAMETER
EXTERNAL PIPING
REFRIGERANT CHARGE
ELECTRICAL
DATA
Liquid mm
(inches)
Gas mm
(inches)
Max
Height
Max
Lenght*
Max
Pipe Bends
Precharge
Kg*
Precharge
lenght
mt.
Additional
charge
g/mt
tonCO
2
eq
precharge*
tonCO
2
eq
max charge*
Operating
current
max
Breaker
A
Breaker
B
200
PUHZ-ZRP
9,52 (3/8")
25,40 (1")
30
100
15
7,10
30
90
4,79
9,05
3
32 A
5 A
250
12,70 (1/2")
25,40 (1")
30
100
15
7,70
120
5,20
11,27
3
32 A
5 A
200
PUHZ-P
9,52 (3/8")
25,40 (1")
30
70
15
6,50
90
4,39
8,64
3
32 A
5 A
250
12,70 (1/2")
25,40 (1")
30
70
15
7,70
120
5,20
9,45
3
32 A
5 A
PUHZ-ZRP / PUHZ-P
P SERIES - OUTDOOR UNIT -
Size 200 to 250
R410A
L
N
Breaker
S1
S2
S3
S1
S2
S3
PUHZ-ZRP
PUHZ-P
PEA-RP_WKA
PEA-M_LA
A
B
L2
L1
L3
N
380V
Breaker
MITSUBISHI ELECTRIC
/ P SERIES R410
Exemple of total additional charge calculation
Formula
∆W(g) = [Lenght of pipes (m) -
Precharge lenght (m)] x additional charge (g/m)
Example
Outdoor unit
= PUZ-ZRP200YKA2
Total pipes lenght
(inlet piping only) = 55 m
Lenght with additional charge
(as tab) = 30 m
Additional charge = 120 g/m
Calculation: ∆W(g) = [55 - 30] x 120 = 3000 g
Summary of Contents for M-SERIES
Page 1: ...Practical installation guide DX ...
Page 2: ......
Page 3: ......
Page 5: ...3 ...
Page 37: ...35 ...
Page 39: ...37 MITSUBISHI ELECTRIC COMMERCIAL ...
Page 49: ...47 ...
Page 61: ...59 MITSUBISHI ELECTRIC REPLACE TECHNOLOGY ...
Page 75: ...73 MITSUBISHI ELECTRIC REPLACE TECHNOLOGY COMMERCIALE ...
Page 76: ...74 Ventilation ...
Page 77: ...75 MITSUBISHI ELECTRIC VENTILATION ...
Page 111: ...109 ...
Page 118: ......
Page 119: ......