66
MITSUBISHI ELECTRIC
/ REPLACE TECHNOLOGY - COMMERCIAL
Commercial line
P SERIES -
PUZ-SM
(2) TWIN SYSTEM
(1) MONOSPLIT SYSTEM
<Table 2> Maximum pipe lenght
SM140(71x2)
Main pipe
(mm) [A]
Liquid pipe
ø9.52
ø9.52
ø12.7
Gas pipe
ø15.88
ø19.05
ø19.05
Branch pipe
(mm) [B, C]
Liquid pipe
ø6.35
Standard size
40m [30m]
40m
[30m]
30m
[15m]
Gas pipe
ø12.7
Liquid pipe
ø9.52
40m
[30m]
40m
[30m]
30m
[15m]
Gas pipe
ø15.88
<Table 1> Maximum pipe lenght (M100, M125, M140)
Liquid pipe
(mm)
OD
ø9.52
ø12.7
Thickness
t0.8
t0.8
Gas pipe
(mm)
OD
ø12.7
ø15.88
ø19.05
ø15.88
ø19.05
Thickness
t0.8
t1.0
t1.0
t1.0
t1.0
SM100
Standard size
30m
[30m]
30m
[30m]
25m
[15m]
25m
[15m]
SM125, SM140
Standard size
40m
[30m]
40m
[30m]
30m
[15m]
30m
[15m]
Marks in the table
: It can be used.
: Cooling capacity is lowered.
: Additional refrigerant charge is required when the pipe lenght
exceeds 20 m.
50m
[30m]
The maximum pipe lenght.
Charge-less pipe lenght.
Summary of Contents for M-SERIES
Page 1: ...Practical installation guide DX ...
Page 2: ......
Page 3: ......
Page 5: ...3 ...
Page 37: ...35 ...
Page 39: ...37 MITSUBISHI ELECTRIC COMMERCIAL ...
Page 49: ...47 ...
Page 61: ...59 MITSUBISHI ELECTRIC REPLACE TECHNOLOGY ...
Page 75: ...73 MITSUBISHI ELECTRIC REPLACE TECHNOLOGY COMMERCIALE ...
Page 76: ...74 Ventilation ...
Page 77: ...75 MITSUBISHI ELECTRIC VENTILATION ...
Page 111: ...109 ...
Page 118: ......
Page 119: ......