Ventilation
A
B
C
D
L
N
1
2
3
1
2
230V
I.M.
(see tab.)
TM1
TM4
PZ-61DR-E
TM2
CN2L
PLA-RP
clean contact
LGH-RVX
TOTAL HEAT EXHANGE VENTILATION SYSTEM
MODEL
Section A
Breaker
Connection B
Connection C
Connection D
Section
Max Lenght
Section
Max Lenght
Section
Max Lenght
LGH-RVX
2x1,5 +T
10 A
2x1
500 m
2x1
500 m
2x1
500 m
Pay attention
1. It is not possible to connect the PZ-61DR-E remote control (connection "B") or an external ON-OFF switch (connection "D") simultaneously with the
Lossnay operating interlock to a Mr. Slim unit ( connection "C");
2. The simultaneous connection of the PZ-61DR-E remote control and an external ON-OFF switch is possible;
3. To interlock the Lossnay operation to a Mr. Slim A control (connection "C") it is necessary to configure the specific function on the latter (see following
pages). The connector for connecting to the Mr. Slim unit is supplied with the Lossnay.
4. Shielded cable maximum length 200 m.
Installation Data*
Conditions of the Mr. SLIM series compatible with the Lossnay ventilation system
TYPE
MODEL
4 way cassette
PLA-BA / SLZ-KA
Ducted
PEAD-JA / PEA-GA /SEZ-KD
*
Horizontal installation only.
TYPE
MODEL
Ceiling
PCA-KA / HA
Wall mounted
PKA-HA / KA
Floor standing
PSA-KA
Summary of Contents for M-SERIES
Page 1: ...Practical installation guide DX ...
Page 2: ......
Page 3: ......
Page 5: ...3 ...
Page 37: ...35 ...
Page 39: ...37 MITSUBISHI ELECTRIC COMMERCIAL ...
Page 49: ...47 ...
Page 61: ...59 MITSUBISHI ELECTRIC REPLACE TECHNOLOGY ...
Page 75: ...73 MITSUBISHI ELECTRIC REPLACE TECHNOLOGY COMMERCIALE ...
Page 76: ...74 Ventilation ...
Page 77: ...75 MITSUBISHI ELECTRIC VENTILATION ...
Page 111: ...109 ...
Page 118: ......
Page 119: ......