6. Status Display and Parameter Setting
6
−
15
(3) Drive unit capacity, motor type and regenerative resistor type selection details
Name Abbr.
Description
TYP
SP039 ATYP Select the capacity of the drive unit to be used.
Setting value
Drive unit model
0000
—
HEX
setting
0001 MDS-B-SPJ2-02
0002 MDS-B-SPJ2-04
0003 MDS-B-SPJ2-075
0004 MDS-B-SPJ2-15
0005 MDS-B-SPJ2-22
0006 MDS-B-SPJ2-37
0007 MDS-B-SPJ2-55
0008 MDS-B-SPJ2-75
0009 MDS-B-SPJ2-110/110C
SP040 MTYP Set the motor to be used. This parameter is valid only when SP034 (SFNC2) - bit 0 is set to 0.
Setting value Motor model Max. speed (rpm) Corresponding drive unit model name
1000
—
—
—
HEX
setting
1001 SJ-P0.2A 10000
MDS-B-SPJ2-02
1002 SJ-P0.4A 10000
MDS-B-SPJ2-04
1003
SJ-P0.75A
10000
MDS-B-SPJ2-075
1004 SJ-P1.5A 10000
MDS-B-SPJ2-15
1005 SJ-P2.2A 8000
MDS-B-SPJ2-22
1006 SJ-P3.7A 8000
MDS-B-SPJ2-37
1007
SJ-PF5.5-01
8000
MDS-B-SPJ2-55
1008
SJ-PF7.5-01
8000
MDS-B-SPJ2-75
1009
SJ-PF11-01
6000
MDS-B-SPJ2-110/110C
SP041 PTYP Select a value from the following table according to the regenerative resistor being used.
Setting value
Regenerative resistor
model
Capacity [W]
Resistance value [
Ω
]
0000
—
—
—
HEX
setting
2000
No
connection
—
—
2100
FCUA-RB04
60
200
2200
FCUA-RB075
80
100
2300
FCUA-RB15
120
60
2400
FCUA-RB22
155
40
2500
FCUA-RB37
185
25
2600
FCUA-RB55
340
20
2700
FCUA-RB75/2
340/680
30/15
(Note 1)
2800
R-UNIT1
700
30
2900
R-UNIT2
700
15
2A00
R-UNIT3
2100
15
2B00
R-UNIT4
2100
10
2C00
R-UNIT5
3100
10
Note 1)
This setting for the FCUA-RB75/2 is used when only one unit is used, or when two units
connected with a parallel connection are used.