1. List of Alarms
1.6 Absolute Position Detection System Alarms
I - 33
Z71 DETECTOR ERROR
(Error No.) (Axis name)
This alarm is displayed if an error is found in
the detector for the absolute position detection
system.
Error No.
Details
Remedy
Zero point
initialization
Alarm reset
when
power is
turned OFF
Servo
alarm No.
0001
The backup voltage in the
absolute position detector
dropped.
Replace the battery‚
check the cable
connections‚ and
check the detector.
Turn the power ON
again‚ and perform
zero point
initialization.
Required
−
(Z70-0101
displays
after power
is turned
ON again.)
25
0003
Communication with the
absolute position detector
was not possible.
Check and replace the
cables‚ card or
detector. Turn the
power ON again‚ and
perform zero point
initialization.
(Required) Only
when detector is
replaced.
Reset 91
0004
The absolute position
data fluctuated when
establishing the absolute
position.
Check and replace the
cables‚ card or
detector. Turn the
power ON again‚ and
perform zero point
initialization.
(Required) Only
when detector is
replaced.
Reset 93
0005
An error was found in the
serial data from the
absolute position
detector.
Check and replace the
cables‚ card or
detector. Turn the
power ON again‚ and
perform zero point
initialization.
(Required) Only
when detector is
replaced.
Reset 92
0006
Servo alarm E3
Absolute position counter
warning
Operation is possible
until the power is
turned off.
(Required) When
power is turned ON
again.
Reset
(Z70-0106
displays
after power
is turned
ON again.)
E3
0007
Initial communication with
the absolute position
detector was not
possible.
Check and replace the
cables‚ card or
detector. Turn the
power ON again‚ and
perform zero point
initialization.
(Required) Only
when detector is
replaced.
Reset 18