1. List of Alarms
1.8 Auxiliary Axis Alarms
I - 41
(7) Z73 AUX SYSTEM WRN
Alarm
information
Details Cause
Remedy
0001
Absolute position
memory battery
voltage warning
Battery voltage drop.
Detector cable wire breakage or
looseness.
• Check the battery and detector
cable. The zero point does not
need to be initialized.
0003
Absolute position
counter warning
An error occurred in the
detector's absolute position
counter.
• Replace the detector.
(8) M00 AUX OPER. ALM
Alarm
information
Details Cause
Remedy
0001
Near-point dog
length insufficient
When executing dog-type
reference point, the zero point
return speed is too fast or the dog
length is too short.
• Lower the zero point return speed
or increase the dog length.
0003
Reference point
return direction
illegal
When executing reference point
return, the axis was moved in the
opposite of the designated
direction.
• Move the axis in the correct
direction.
0004
External interlock
The axis interlock function is
valid.
• Cancel the interlock signal
0005
Internal interlock
An interlock was established by
the servo OFF function.
• Cancel the servo OFF.
0007
Soft limit
The soft limit was reached.
• Check the soft limit setting and
machine position
0024
In absolute
position alarm.
Reference point
return not possible.
Reference point return was
executed during an absolute
position alarm.
• Initialize the absolute position
reference point and then fix the
absolute position coordinates.
0025
In initializing
absolute position.
Reference point
return not possible.
Reference point return was
executed while initializing the
absolute position.
• Initialize the absolute position
reference point and then fix the
absolute position coordinates.