3. Program Error
I - 68
Error No.
Details
Remedy
P155
F-CYC ERR (CC)
A fixed cycle command has been issued
in the radius compensation mode.
• The radius compensation mode is
established when a fixed cycle command is
executed and so the radius compensation
cancel command (G40) should be issued.
P156
BOUND DIRECT
At the start of G46 nose R compensation‚
the compensation direction is undefined
if this shift vector is used.
• Change the vector to that with which the
compensation direction is defined.
• Exchange with a tool having a different tip
point number.
P157
SIDE REVERSED
During G46 nose R compensation‚ the
compensation direction is inverted.
• Change the G command to that which allows
inversion of the compensation direction (G00‚
G28‚ G30‚ G33‚ or G53).
• Exchange with a tool having a different tip
point number.
• Turn ON the #8106 G46 inversion error
avoidance parameter.
P158
ILLEGAL TIP P.
During G46 nose R compensation‚ the tip
point is illegal (other than 1 to 8).
• Change the tip point number to a legal one.
P170
NO CORR. No.
The compensation number (DOO‚ TOO‚
HOO) command was not given when the
radius compensation (G41‚ G42‚ G43‚
G46) command was issued.
Alternatively‚ the compensation number
is larger than the number of sets in the
specifications.
• Add the compensation number command to
the compensation command block.
• Check the number of compensation number
sets a correct it to a compensation number
command within the permitted number of
compensation sets.
P172
G10 L-No. ERR
(G10 L-number error)
The L address command is not correct
when the G10 command is issued.
• Check the address L-Number of the G10
command and correct the number.
P173
G10 P-No. ERR
(G10 compensation error)
When the G10 command is issued‚ a
compensation number outside the
permitted number of sets in the
specifications has been commanded for
the compensation number command.
• First check the number of compensation sets
and then set the address P designation to
within the permitted number of sets.
P177
LIFE COUNT ACT
Registration of tool life management data
with G10 was attempted when the used
data count valid signal was ON.
• The tool life management data cannot be
registered when counting the used data. Turn
the used data count valid signal OFF.