Chapter 11 Troubleshooting
11–26
Alarm check timing
f1 f2 f3 f4
Alarm No.
80
HR unit connection error:
An incorrect connection or cable breakage was detected in the MDS-B-HR
connected to the MAIN side.
–
{
{
{
Investigation details
Investigation results
Remedies
The connector is disconnected (or
loose).
Correctly install.
1 Wiggle the connectors by hand to check
whether the MDS-B-HR connectors (unit
side, HR side and linear scale side) are
disconnected.
The connector is not disconnected.
Investigate item 2.
There is a connection fault.
Replace the communication cable.
2 Turn the power OFF, and check the
connection of the detector cables
(between driver I/F units and between
I/F unit and scale) with a tester.
The connection is normal.
Investigate item 3.
The alarm is on the unit side.
Replace the drive unit.
3 Connect with another normal axis unit
(or MDS-B-HR) and check whether the
fault is on the unit side or MDS-B-HR
(linear scale) side.
The alarm is on the MDS-B-HR (linear
scale) side.
Investigate item 4.
No abnormality is found in particular.
Replace MDS-B-HR (linear scale).
4 Check if there is any abnormality in the
unit's ambient environment.
(Ex. Ambient temperature, noise,
grounding)
An abnormality was found in the
ambient environment.
Take remedies according to the causes of
the abnormality.
Ex.
High
temperature ...
Check the
cooling
fan.
Incomplete grounding …. Additionally
ground.
Alarm check timing
f1 f2 f3 f4
Alarm No.
81
HR unit HSS communication error:
The MDS-B-HR connected to the MAIN side detected an error in the communication
with the absolute position linear scale.
–
{
{
{
Investigation details
Investigation results
Remedies
1 Check the alarm No. "80" items.
CAUTION
To prevent trouble, when changing the motor and driver combination, avoid
driving a driver with a larger capacity than the specified driver using the motor.
The motor could be demagnetized. Note that this combination can be used for
checking in the emergency stop state. The motor can be driven with a driver
with a capacity smaller than the specifications.