JEP0-IL9537
2.2. General specification (COC4-A02S1)
Table 2-2 General specification (COC4-A02S1)
Name
Overcurrent Relay
Relay Model
COC4-A02S1
Style
562PQB
Elements
Protection
IDMT overcurrent (51)
Instantaneous overcurrent (50)
IDMT ground overcurrent (51N)
Instantaneous ground overcurrent (50N)
Rating
Frequency
50Hz / 60Hz (selectable)
Voltage
AC5A
Aux. power
supply
Voltage
AC100V
– 110V
DC100V
– 125V *1
Operative range
AC: 85
–126.5 V
DC: 85-143 V *1
Setting
IDMT-OC
(51)
Operation value LOCK
– 1.0 ~ 12.0 A (0.1 A step) *2
Time Multiplier
0.25
– 0.5 ~ 50.0 (0.5 step)
IDMT curve
NI01-VI01-EI01-LI01-DT01-DT(Inst.) -NI11-EI11
-EI12-NI21-VI21-LI21-MI31-NI31-VI31-EI31
* DT(Inst.): less than or equal to 50 ms
* In front LED, quantified value are indicated.
Inst.-OC (50)
Operation value LOCK
– 10.0 ~ 80.0 A (0.5 A step) *2
Operation time
INST (less than or equal to 40 ms)
Ground IDMT
OC (51N)
Operation value LOCK
– 0.25 ~ 4.00 A (0.05 A step) *2
Time Multiplier
0.25
– 0.5 ~ 50.0 (0.5 step)
IDMT curve
NI01-VI01-EI01-LI01-DT01-DT(Inst.) -NI11-EI11
-EI12-NI21-VI21-LI21-MI31-NI31-VI31-EI31
* DT(Inst.): less than or equal to 50 ms
Ground inst.
OC (50N)
Operation value LOCK
– 2.0 ~ 20.0 A (0.5 A step) *2
Operation time
INST (less than or equal to 40 ms)
Forced
operation
Trip and control (annunciator) contacts can be forced to operate.
Operation
indication
Operation indicator LED comes on when the relay element operates.
LED indication: A-Phase, B-Phase, C-Phase, Zero-sequence, Instantaneous overcurrent element.
Display
RUN LED (green)
Indicate the result of automatic self-diagnosis. This LED is turned
on for normal and turned off for abnormal.
ALARM LED (red)
Indicate the result of automatic self-diagnosis. This LED is turned
off for normal and turned on for abnormal.
Self-diagnosis
(ALARM)
An electronic circuit and a built-in power supply are always supervised, and it outputs to the
RUN/ALARM LED and an ALARM contact.
Burden
Voltage Circuit
0.5VA or less (with 110VAC)
1.0VA or less (with 220VAC)
Auxiliary supply
For 110VDC : approx. 1.6W
For 110VAC : approx. 1.9VA
Output Contact Configuration For trip
Normally open contact
For control
Normally open contact (for IDMT-OC, Inst.-OC and Ground-OC)
For alarm
Normally close contact
Capacity
For trip
Make:
110 VDC, 15 A, 0.5 s (L/R=0 s)
220 VDC, 10 A, 0.5 s (L/R=0 s)
Break:
110 VDC, 0.3 A (L/R
≦
40 ms)
220 VDC, 0.15 A (L/R
≦
40 ms)
Continuation: 1.5 A