Characteristics

 

Item 

Characteristics

 

Standard use 
conditions 

Ambient temperature: 

20 to +60

 (Under the state where dew condensation or freezing does not occur) 

Relative humidity: 30 to 80% on daily average 
Altitude: 2000m or lower 

The state where abnormal vibration, shock, and inclination are not applied. 

The state where it is not exposed to harmful gas, excessive dust, and water droplet or vapor. 

Operation value 
characteristics 

Setting: Operating time = Minimum 
Criteria: Within 

±

5% of each setting value 

Reset value 
characteristics 

Setting: Operating time = Minimum 
Criteria: 95% or more of operating value 

Operating time 
characteristics 

Setting: Operation value = Minimum 
Input: 0V 

 120% of setting value 

Criteria: 

0.1

0.2s setting 

Within 

±

50ms of setting time 

0.5s or more setting 

Within 

±

10% of setting time 

Setting: Operation value = Minimum 
Input: 110V 

 120% of setting value 

Criteria: 

0.1s setting 

Within 

±

20ms of setting time 

0.2s or more setting 

Within 

±

10% of setting time 

Resetting time 
characteristics 

Setting: Operation value = Minimum 
Input: 120% of setting value 

 0V 

Criteria: 250ms

±

50ms 

Frequency 
characteristics 

Frequency variations: 

±

5% of rated frequency 

Setting: Operation value = Minimum, Operating time = Minimum 
Operation value: Within 

±

5% of the value at rated frequency 

Temperature 
characteristics 

Setting: Operation value = Minimum, Operating time = Minimum 
Operation value at ambient temperature of 0, +40

: Within 

±

5% of the value at 20

 

Operation value at ambient temperature of -20, +60

: Within 

±

10% of the value at 20

 

Distorted wave 
characteristics 

Setting: Operation value = Minimum, Operating time = Minimum 
3rd, 5th, and 7th harmonic content: 90% of fundamental wave 

Criteria for operation value: Within ±1

0% of the value at fundamental wave only 

Guaranteed 
maximum voltage 

Setting: Operation value = Maximum, Operating time = Minimum 
Input: 0V 

 165V for 10s 

Criteria: The relay shall operate. 

Vibration

 

 

Frequency 

(Hz) 

Peak-to-peak amplitude  mm 

(Acceleration  m/s

2

Vibration 

time 

(s) 

Setting:  Minimum  operation  value  and 
minimum operating time 
Input: 90% of setting value 
Criteria: No malfunction and no abnormal 
indication 

Forward/ 
backward 

Right/left 

Up/down 

10 

5 (10) 

2.5 (5) 

30 

16.7 

0.4 (2) 

600 

Shock 

Maximum acceleration: 300m/s

2

 

Direction: 3 directions in forward/backward, right/left, and up/down 
Criteria: No abnormality when applying three shocks in each direction 

Insulation 
resistance 

Test circuit: Between all circuits and  external box,  between separate circuits, and between the poles  of 
contacts 
Criteria: More than 10M

Ω

 by DC500V megger. 

(Note) The test is held under the condition that relative humidity is less than 80%. 

Withstand 
voltage 

Between all circuits and external box: AC2000V, for 1 minute 
Between separate circuits: AC2000V, for 1 minute 
Between the poles of contacts (a11-a12, a21-a22): AC1000V for 1 minute 

Lightning 
impulse 
withstand 
voltage 

Apply standard waveform 

(1.2/50 μs)

 to positive/negative pole for 3 times respectively. 

Between all circuits and external box, between VT circuit and control circuit: 4.5kV 
Between terminals of VT circuit, between mutual control circuits: 3.0kV 
Criteria: No abnormality 

Noise-proof 

Apply damped oscillatory wave prescribed in JEC-2501 for 2 seconds. 

Between all VT circuits and external box 

Between all control circuits and external box 

Setting: Operation value = 120V, Operating time = Minimum 
Input: Rated voltage 
Criteria: No malfunction 

Radio 
disturbance 

Intermittently irradiate radio waves to the front panel of the relay with a transceiver of 150MHz or 400MHz 
band (5W output) from a distance of 0.5m. 
Setting: Operation value = 120V, Operating time = Minimum 
Input: Rated voltage 
Criteria: No malfunction 

Contact capacity 

 

Making 

(Closing) 

DC110V 15A (L/R=0ms) 
DC220V 10A (L/R=0ms) 

AC110V 10A (cosφ=0.1)

 

Breaking 

(Opening) 

DC110V 0.3A (L/R=7ms) 

AC110V 5A (cosφ=0.1)

 

AC220V 1A 

(cosφ=0.1)

 

Note) For details, refer to JEC 2520 (2018).

 

 

Summary of Contents for MELPRO MOV-A3V-R

Page 1: ...1 JEP0 IL9557 Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager ...

Page 2: ...t Failure to do so may lead to the risk of electric shock equipment failure malfunction or failure to operate Ensure that the equipment is connected correctly in accordance with the details e g polarity or phase sequence shown on the connection terminals Otherwise there is the risk of failure burning malfunction or maloperation All power supplies and transformers to the equipment must be of suitab...

Page 3: ...el Otherwise there are risks of electric shock injury failure malfunction and maloperation Handling and maintenance of the equipment must only be carried out after gaining a thorough understanding of the instruction manual Otherwise there is the risk of electric shock injury failure malfunction or maloperation When replacing the equipment use a product of same model rating and specifications Other...

Page 4: ... special damages and secondary damages whether foreseeable or not compensation for accidents and compensation for damages to products other than MITSUBISHI ELECTRIC CORPORATION products and other tasks 4 Applications of products 1 The user is requested to confirm the standards the regulations and the restrictions which should be applied in case of utilizing this product and another one in combinat...

Page 5: ...ecommended to replace 2 Product supply including repair parts is not available after production is discontinued 6 Changes in product specification The specification given in the catalogue manuals or technical documents are subject to change without prior notice 7 Scope of service The technical service fee such as engineer dispatching fee is excluded in the price of our products Please contact to o...

Page 6: ...0 5 0s Frequency 50Hz SW1 ON 60Hz SW1 OFF Display Self monitoring The RUN indicator green color is lighted in normal condition Operation indicator The indicator turns from black into orange color when the protection element is put into operation Manual resetting type Numerical display 1 Lo means LOCK setting the protection element is locked Indication item Range Voltage measurement 80 160V Pickup ...

Page 7: ...m Input 0V 165V for 10s Criteria The relay shall operate Vibration Frequency Hz Peak to peak amplitude mm Acceleration m s2 Vibration time s Setting Minimum operation value and minimum operating time Input 90 of setting value Criteria No malfunction and no abnormal indication Forward backward Right left Up down 10 5 10 2 5 5 30 16 7 0 4 2 600 Shock Maximum acceleration 300m s2 Direction 3 directio...

Page 8: ...p When input voltage is greater than or equal to the setting value U is displayed This function can be used for operation value tests CPU reset button While this button is pressed the relay function is locked and the RUN indicated LED is turned off RUN indicated LED Green It shows the result of self monitoring It lights up in normal condition Setting switches for operation value and time Set the s...

Page 9: ...after the relay operation Clearing of fault records Set indicator select switch to CLEAR FAULT REC and hold for 5s or more then O K is displayed and all of the fault record are cleared 5 Display function of setting change When a setting is changed the setting value after changing is displayed for approx 3s preferentially 6 Detection function of frequency difference If there is a difference between...

Page 10: ...conditions Please refrain from changing the setting value during operation since unwanted operation may occur However if the setting change is unavoidable please press the CPU reset button in order to lock the relay function Don t leave rotary switches with halfway indefinite state The RUN LED lights up in the normal condition when the rated voltage is input If it still turns off when the input vo...

Page 11: ...there is no problem Voltage applied terminals External box Fixing screw for mounting b Apply 2000V AC commercial frequency between separate circuits for one minute and make sure that there is no problem Voltage applied terminals 3 Operation characteristics test When the rated voltage is applied the RUN display LED green lights up This indicates that the relay works properly When adjusting the test...

Page 12: ...the electrical circuit e g substrate capacitor and transformer and be sure to hold the drawer handle or the frame part when transporting Touching the electrical circuit may cause electric shock or damage to the circuit Before the subunit is to be drawn out ensure that the following items are checked in order not to carry out the work in hot line condition Lock of the tripping circuit Turning off t...

Page 13: ...the subunit with your finger hooked on the drawer handle on both sides Support the frame of subunit and pull out 2 Procedure of housing Drawer fixing screw Support the frame of subunit and place the subunit in the case along the rails Insert the subunit into the case horizontally Open the cover and tighten the drawer fixing screw Cover Cover ...

Page 14: ...up the upper side of the cover from the inner surface Then remove from the protrusion of the body Installing the cover As shown in Fig 5 7 mount the holes on the upper side of the cover to the protrusion of the body Then press down lightly on the lower side of the cover and mount to the protrusion of the body in the same way as above When replacing the cover during operation be careful not to touc...

Page 15: ...ed to the protection relay have limited lifetime which will bring the degradation to the relay The degree of degradation will be variable depending on the purpose aging usage environment and unevenness on the performance of each part Our company designs its products so that the recommended renewal period is 15 years or more However there may be some possibilities to occur any failures before reach...

Page 16: ...HEAD OFFICE 7 3 MARUNOUCHI 2 CHOME CHIYODA KU TOKYO 100 8310 JAPAN First edition Jan 2021 ...

Reviews: