background image

1.2

External dimensions/weight

Main units

FX

2NC

 input/output extension blocks (Connector type)

FX

2NC

 input/output extension blocks (Terminal block type)

2.

General specifications and Installation

For more details, refer to the FX

3UC

 Series User's Manual -

Hardware Edition

Type

Model name

W:mm 

(inches)

MASS 

(Weight):

 kg (lbs)

Main units

FX

3UC

-16MT/D(SS)

34.0 (1.34)

0.2 (0.44)

FX

3UC

-32MT/D(SS)

34.0 (1.34)

0.2 (0.44)

FX

3UC

-64MT/D(SS)

59.7 (2.36)

0.3 (0.66)

FX

3UC

-96MT/D(SS)

85.4 (3.37)

0.35 (0.77)

Input/output
extension
blocks
(Connector
type)

FX

2NC

-16EX(-DS)

14.6 (0.57)

0.15 (0.33)

FX

2NC

-32EX(-DS)

26.2 (1.03)

0.2 (0.44)

FX

2NC

-16EYT(-DSS)

14.6 (0.57)

0.15 (0.33)

FX

2NC

-32EYT(-DSS)

26.2 (1.03)

0.2 (0.44)

Input/output
extension
blocks
(Terminal
block type)

FX

2NC

-16EX-T(-DS)

20.2 (0.57)

0.15 (0.33)

FX

2NC

-16EYR-T(-DS)

24.2 (0.95)

0.2 (0.44)

Unit: mm(inches)

90(3.54")

74(2.91")

(13)

(0.52")

W

W

Unit: mm(inches)

90(3.54")

74(2.91")

(13)

(0.52")

W

Unit: mm(inches)

90(3.54")

74(2.91")

15

(0.6")

INSTALLATION 
PRECAUTIONS

Make sure to cut off all phases of the power supply externally
before attempting installation or wiring work. 
Failure to do so may cause electric shock or damage to the
product.

INSTALLATION 
PRECAUTIONS

Use the product within the generic environment specifications
described in section 2.1 of this manual.
Never use the product in areas with excessive dust, oily smoke,
conductive dusts, corrosive gas (salt air, Cl

2

, H

2

S, SO

2

 or NO

2

),

flammable gas, vibration or impacts, or expose it to high
temperature, condensation, or rain and wind.
If the product is used in such conditions, electric shock, fire,
malfunctions, deterioration or damage may occur.

Do not touch the conductive parts of the product directly. 
Doing so may cause device failures or malfunctions.

Install the product securely using a DIN rail or mounting
screws.

Install the product on a flat surface.
If the mounting surface is rough, undue force will be applied to
the PC board, thereby causing nonconformities.

When drilling screw holes or wiring, make sure that cutting and
wiring debris do not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or
malfunctions.

Be sure to remove the dust proof sheet from the PLC's
ventilation port when installation work is completed. 
Failure to do so may cause fire, equipment failures or
malfunctions.

Connect the extension cables, peripheral device cables, input/
output cables and battery connecting cable securely to their
designated connectors.
Unsecured connection may cause malfunctions.

Turn off the power before attaching or detaching the following
devices.
Failure to do so may cause device failures or malfunctions.
- Peripheral devices, extension blocks, connector conversion

adapter, extension power supply units, special adapters, and
FX Series terminal blocks

- Battery and memory cassettes

Notes

When a dust proof sheet is supplied with an extension unit/

block, keep the sheet applied to the ventilation slits during

installation and wiring work.

To prevent temperature rise, do not install the PLC on a floor, a
ceiling or a vertical surface.
Install it horizontally on a wall as shown in section 2.2.

Keep a space of 50mm (1.97”) or more between the unit main
body and another device or structure (section 2.2 part A). Install
the unit as far away as possible from high-voltage lines, high-
voltage devices and power equipment.

2.1

Generic specifications [Main unit]

*1 For common grounding, refer to section 3.2.
*2 The PLC cannot be used at a pressure higher than the

atmospheric pressure to avoid damage.

2.2

Installation location

Install the PLC in an environment conforming to the generic
specifications (section 2.1), installation precautions and notes.

For more details, refer to FX

3UC

 Series User's Manual -

Hardware Edition.

Installation location in enclosure 

Space in enclosure

Extension devices can be connected on the left and right sides of the
PLC main unit.
If you intend to add extension devices in the future, keep extra space
on the left and right sides open.

2.3

Procedures for installing to and detaching from 
DIN rail

The main unit can be installed on a DIN46277 rail [35mm (1.38”)
wide].
(It cannot be installed directly with screws.)

2.3.1

Installing methods

1) Turn the power supply OFF.
2) Push the DIN rail mounting hooks

1

 of all connected units/blocks as

shown in the figure on the right 

.

Item

Specification

Ambient
temperature

0 to 55

°

C (32 to 131

°

F) when operating and -25 to

75

°

C (-13 to 167

°

F) when stored

Ambient
humidity

5 to 95%RH (no condensation) when operating

Vibration
resistance

Fre-

quency

(Hz)

Accel-

eration

(m/s

2

)

Half 

ampli-

tude

(mm)

Sweep Count 
for X, Y, Z: 10 
times 
(80 min. in 
each direction)

When
installed
on DIN
rail

10 to 57

-

0.035

57 to 

150

4.9

-

Shock
resistance

(147m/s

2

 Acceleration, Action time: 11ms, 3 times by

half-sine pulse in each direction X, Y, and Z)

Noise
resistance

By noise simulator at noise voltage of 1,000Vp-p,
noise width of 1

µ

s, rise time of 1ns and period of 30 to

100Hz

Dielectric
withstand
voltage

500V AC for one
minute

Comply with JEM-1021

Between batch of all terminals
and ground terminal

Insulation
resistance

5M

 or more by

500V DC megger

Grounding

Class D grounding (grounding resistance: 100

 or

less) <Common grounding with a heavy electrical
system is not allowed.>

*1

Working
atmosphere

Free from corrosive or flammable gas and excessive
conductive dusts

Working
altitude

<2000m

*2

A

Configuration without extension cable

A

A

A

FX

3U

C

M

a

in

 uni

t

FX

2N

C

-16E

X

FX

2N

C

-1

6EYT

50mm

(1.97")

A

Configuration with extension cable

FX

2N

-1

0P

G

FX

0N

-65EC

FX

0N

-30EC

FX

2N

-CNV-BC

Other

equi

pm

ent

Other

equipment

Other

equipment

A

A

A

A

≥ 

50mm

(1.97")

A

A

A

A

FX

3U

C

M

ain unit

FX

2N

C

-16E

X

FX

2N

C

-C

N

V

-I

F

FX

3U

-4

AD

-AD

P

A

A

Summary of Contents for MELSEC FX3U-485ADP-MB

Page 1: ...the PLC is transported with the BAT LED on or the battery exhausted the battery backed data may be unstable during transportation The PLC is a precision instrument During transportation avoid impacts larger than those specified in Section 2 1 Failure to do so may cause failures in the PLC After transportation verify the operations of the PLC STARTUP AND MAINTENANCE PRECAUTIONS Models MELSEC FX2N s...

Page 2: ...e standard Radiated Emissions Mains Terminal Voltage Emissions RF immunity Fast Transients ESD Surge Voltage drops and interruptions Conducted Power magnetic fields Standard Remark IEC1010 1 1990 A1 1992 BSEN61010 1 1993 Safety requirements for electrical equipment for measurement control and laboratory use General requirements The equipment has been assessed as a component for fitting in a suitab...

Page 3: ...eries terminal blocks Battery and memory cassettes Notes When a dust proof sheet is supplied with an extension unit block keep the sheet applied to the ventilation slits during installation and wiring work To prevent temperature rise do not install the PLC on a floor a ceiling or a vertical surface Install it horizontally on a wall as shown in section 2 2 Keep a space of 50mm 1 97 or more between ...

Page 4: ... lower connector when performing crossover wiring for the later block In case of the FX2NC EX T DS removal of the connector cover is unnecessary Black Black Red Red Green Ground a Press here Self made power cable To use self made power cables use the following wire and connector suggestions 2 5 Connection to input output connector The input output connectors of the Main units conform to MIL C 8350...

Page 5: ...put output wiring 50 to 100m 164 1 to 328 1 long will cause almost no problems of noise but generally the wiring length should be less than 20m 65 7 to ensure the safety Extension cables are easily affected by noise Lay the cables at a distance of at least 30 to 50mm 1 19 to 1 97 away from the PLC output and other power lines Item Specification Supply voltage 24V DC 20 15 1 Ripple Voltage p p 5 or...

Page 6: ...ing For more details refer to the FX3UC Series User s Manual Hardware Edition 3 4 1 Transistor output specifications 1 When using an instruction related to pulse train output or positioning make sure to set the load current to 10 to 100mA 5 to 24V DC 2 The transistor OFF time is longer under lighter loads For example under a load of 24V DC 40mA the response time is approx 0 3ms When response perfo...

Page 7: ...rve simultaneous ON ratio 80 55 C Ambient temperature applicable 20 45 C When extension blocks units are connected Supply voltage 24V DC 40 C 60 65 When only the main unit is used without extension blocks units 3 5 3 Cautions on relay output wiring For more details refer to FX3UC Series User s Manual Hardware Edition 1 Protection circuit for load short circuits A short circuit at a load connected ...

Page 8: ... Y2 Y3 Y4 Y5 Y6 Y7 V1 V1 Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 OUT Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 V0 V0 Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 Lower Notch Upper IN X0 X1 X2 X3 X4 X5 X6 X7 COM COM COM X0 X1 X2 X3 X4 X5 X6 X7 COM Lower Upper OUT Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 COM1 COM1 COM2 Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 COM2 Lower Upper This manual confers no industrial property rights or any rights of any other kind nor does it confer any patent ...