10 SETTING PARAMETERS
10.2 Setting Network Parameter
105
10
*1 When selecting "RECV Function", set "No Setting" for "RECV Function Reception Buffer" in the driver setting.
2.
Click the [End] button.
Combination of detection method and event condition
The following table shows results and events of the combination of detection method and event condition.
Event Condition
Set the event condition. (
Page 105 Combination of detection method and event condition)
Word Device Setting Value
Set the word device setting value.
DEC setting range: 0 to 65535
HEX setting range: 0000 to FFFF
Channel No.
Set the channel number (use for dedicated instructions) .
Setting range: 1 to 2
Event No.
Set the event number.
Setting range: 0 to 15
[Clear] button
Clears all settings.
[Check] button
Checks whether the settings are correct.
Device
Detection Method
Event Condition
Description
RX
RY
SB
Edge Detect
ON
An event occurs at the rising edge of the device.
OFF
An event occurs at the falling edge of the device.
Level Detect
ON
An event occurs by turning ON the device.
OFF
An event occurs by turning OFF the device.
RWw
RWr
SW
Edge Detect
Equal
An event occurs when values match. (First time only)
Unequal
An event occurs when values do not match. (First time only)
Change
An event occurs when values change. (First time only)
Level Detect
Equal
An event occurs when values match.
Unequal
An event occurs when values do not match.
RECV Function
Edge Detect
An event occurs when a specified channel receives data.
Item
Description
Summary of Contents for MELSEC Q80BD-J71GF11-T2