16 TROUBLESHOOTING
16.9 Error Code List
171
16
D257H
Request type error (REQ)
Check the request type in the request data, and retry the operation.
If this error persists, please consult your local Mitsubishi representative.
D258H
Specified/current control station not
exist (dedicated instruction)
Check the target station number, and retry the operation.
If this error persists, please consult your local Mitsubishi representative.
D259H
Mode error during dedicated
instruction execution
Change the mode of the master station from "Loop test" to "Online", and execute it again.
If this error persists, please consult your local Mitsubishi representative.
D25AH
Channel in use (dedicated
instruction)
Retry it after a little while.
Change the channel for the own or target station.
D25BH
Channel in use (dedicated
instruction)
Change the channel for the own or target station.
D25CH
Dedicated instruction error
An invalid value is set for the control block of the dedicated instruction. Correct the value, and then retry
the operation.
If this error persists, please consult your local Mitsubishi representative.
D25DH
Incorrect transient data
Check the transient data at the request source, and retry the operation.
If this error persists, please consult your local Mitsubishi representative.
D25EH
Dedicated instruction error
Another CC-Link dedicated instruction is in execution. Retry it after a little while.
If this error persists, please consult your local Mitsubishi representative.
D25FH
Station type error (REMFR/REMTO
executing station)
The REMFR/REMTO instruction is not available for stations other than master and local stations. Modify
the program so that the REMFR/REMTO instruction will not be used.
D260H
Station type error (REMTO
executing station)
The REMTO instruction is not available for local stations. The REMTO instruction must be executed on
the master station.
D261H
Station type error (CCPASET
executing station)
Parameter setting using the CCPASET instruction is not available for local stations. It must be executed
to the master station.
D262H
Number of total slave stations setting
error (CCPASET)
Correct the number of total slave stations in the control data, and retry the operation.
If this error persists, please consult your local Mitsubishi representative.
D263H
Constant link scan time setting error
(CCPASET)
Correct the constant link scan time in the control data, and retry the operation.
If this error persists, please consult your local Mitsubishi representative.
D264H
Station No. range error (CCPASET)
Change the station number in the setting data to any of 1 to 120, and retry the operation.
If this error persists, please consult your local Mitsubishi representative.
D265H
Duplicate station No. (CCPASET)
Correct the station number in the setting data, and retry the operation.
If this error persists, please consult your local Mitsubishi representative.
D266H
Number of total slave stations error
(CCPASET)
Correct the number of total slave stations in the setting data, and retry the operation.
If this error persists, please consult your local Mitsubishi representative.
D267H
Station type error (CCPASET)
Change the station type value in the setting data to any of 0 to 3, and retry the operation.
If this error persists, please consult your local Mitsubishi representative.
D268H
Device range assignment error
(CCPASET)
Correct the link device offset or size of slave station(s) in the setting data, and retry the operation.
If this error persists, please consult your local Mitsubishi representative.
D269H
Target station type error
Set the target station number in the REMFR/REMTO instruction to the station number of an intelligent
device station.
D26AH
Target station No. error
Reconnect the target station of the REMFR/REMTO instruction.
D26BH
Network No. error (CCPASET
executing station)
Set any of 1 to 239 to Switch 1 (network No.) in the intelligent function module switch setting of the
master/local module.
D26CH
Station No. error (CCPASET
executing station)
When activating as a master station, set 0 to Switch 2 in the intelligent function module switch setting of
the master/local module.
When activating as a local station by the CCPASET instruction, use a master/local module with a serial
number whose first five digits are '12072' or higher.
When activating as a local station, set a value within the range from 3101H to 3178H to Switch 2 in the
intelligent function module switch setting of the master/local module.
D26DH
Mode error (CCPASET executing
station)
Set 0 to Switch 3 in the intelligent function module switch setting of the master/local module
D280H
Transient data request error
Correct the request command at the request source, and retry the operation.
D281H
Transient reception failed
Check the network condition by CC-Link IE Field Network diagnostics, and take action.
When the target station is overloaded and cannot receive transient data, send the data to the target
station after the load on the station is reduced.
D282H
Receive queue full
Temporarily stop the transient transmission, and then retry the operation.
Reduce the frequency of transient transmission and then retry the operation.
Use the COM instruction to increase the frequency of transient transmission.
If this error persists, please consult your local Mitsubishi representative.
D283H
Transient transmission failed
Check the network condition by CC-Link IE Field Network diagnostics, and take action.
Exchange the cables between PORT1 and PORT2 of the request source and retry the operation.
Reduce the frequency of transient transmission and then retry the operation.
Error
code
Error code
Corrective action
Summary of Contents for MELSEC Q80BD-J71GF11-T2
Page 2: ......
Page 6: ...4 Disposal Precautions CAUTION When disposing of this product treat it as industrial waste ...
Page 118: ...116 12 MONITORING MEMO ...
Page 140: ...138 14 MELSEC DATA LINK LIBRARY MEMO ...
Page 142: ...140 15 PROGRAMMING 15 1 Precautions on Programming MEMO ...
Page 243: ...241 I U Utility 83 ...
Page 247: ......