64
5 FUNCTIONS
5.2 Cyclic Transmission
Assurance of cyclic data integrity
The cyclic data integrity can be assured in 32-bit units or for each station.
32-bit data assurance
The RWw and RWr data can be assured in 32-bit units.
■
Setting method
Disable "Block Data Assurance per Station" on the "Supplementary Setting" screen in "Network Configuration Setting".
(
Page 102 Supplementary setting)
To enable 32-bit data assurance, disable "Block Data Assurance per Station".
■
Access to cyclic data
When accessing link refresh target devices, the integrity of the 32-bit data can be assured by accessing RWw and RWr with
the following conditions satisfied.
• Start device number of RWw/RWr is a multiple of 2.
• The number of points assigned to RWw/RWr is a multiple of 2.
For data assurance of more than 32 bits, use the block data assurance per station or interlock programs.
Clear the check box.