108
10 SETTING PARAMETERS
10.2 Setting Network Parameter
Routing parameters
Set communication paths for transient transmission between a station in the own network and stations in other networks.
Window
[View]
[Network Parameter]
"CC IE Field Number of Boards Setting" screen
[Routing Parameters] button
Operating procedure
1.
Set the items on the screen.
2.
Click the [End] button.
Item
Description
Target Network No.
Set the target network number. Numbers cannot be overlapped.
Setting range: 1 to 239
Relay Network No.
Set the first relay network number in the path to the target network.
Setting range: 1 to 239
Relay Station No.
Set the first relay station number in the path to the target network.
Setting range: 0 to 120
Condition Setting of Relay/Target
Network
Set whether MELSECNET/10 network is to be used for routing the network.
[Clear] button
Clears all settings.
[Check] button
Checks whether the settings are correct.
Summary of Contents for MELSEC Q80BD-J71GF11-T2
Page 2: ......
Page 6: ...4 Disposal Precautions CAUTION When disposing of this product treat it as industrial waste ...
Page 118: ...116 12 MONITORING MEMO ...
Page 140: ...138 14 MELSEC DATA LINK LIBRARY MEMO ...
Page 142: ...140 15 PROGRAMMING 15 1 Precautions on Programming MEMO ...
Page 243: ...241 I U Utility 83 ...
Page 247: ......