234
APPX
Appendix 15 EMC and Low Voltage Directives
Appendix 15
EMC and Low Voltage Directives
Compliance with the EMC Directive, which is one of the EU directives, has been mandatory for the products sold within EU
member states since 1996 as well as compliance with the Low Voltage Directive since 1997. To prove the compliance,
manufactures must issue an EC Declaration of Conformity and the products must bear a CE marking.
Sales representative in EU member states
The authorized representative in EU member states will be:
Company name: Mitsubishi Electric Europe BV
Address: Mitsubishi-Electric-Platz 1, 40882 Ratingen, Germany
Measures to comply with the EMC Directive
The EMC Directive sets two requirements for compliance: emission (conducted and radiated electromagnetic energy emitted
by a product) and immunity (the ability of a product to not be influenced by externally generated electromagnetic energy).
This section summarizes the precautions for machinery constructed with the CC-Link IE Field Network board to comply with
the EMC Directive.
These precautions are based on the requirements of the EMC Directive and the harmonized standards. However, they do not
guarantee that the entire machinery constructed according to the descriptions complies with the EMC Directive.
The manufacturer of the machinery must determine the testing method for compliance and declare conformity to the EMC
Directive.
EMC Directive related standards
■
Emission requirements
*1 The tests were conducted installed in a control panel.
*2 QP: Quasi-Peak value, Mean: Average value
Standard
Test item
Test description
Value specified in standard
EN61131-2: 2007
CISPR16-2-3
Radiated emission
The electromagnetic wave which the product emits to
the external space is measured.
• 30 to 230 MHz,
QP: 40 dB
μ
V/m (measured at 10 m
distance)
• 230 to 1000 MHz,
QP: 47 dB
μ
V/m (measured at 10 m
distance)
CISPR16-2-1, CISPR16-1-2
Conducted emission
The noise level which the product emits to the power
line is measured.
• 0.15 to 0.5 MHz,
QP: 79 dB, Mean: 66 dB
• 0.5 to 30 MHz,
QP: 73 dB, Mean: 60 dB
Summary of Contents for MELSEC Q80BD-J71GF11-T2
Page 2: ......
Page 6: ...4 Disposal Precautions CAUTION When disposing of this product treat it as industrial waste ...
Page 118: ...116 12 MONITORING MEMO ...
Page 140: ...138 14 MELSEC DATA LINK LIBRARY MEMO ...
Page 142: ...140 15 PROGRAMMING 15 1 Precautions on Programming MEMO ...
Page 243: ...241 I U Utility 83 ...
Page 247: ......